10

CONTROL PANEL

7

BEFORE STARTING

6

BE SURE TO MAKE THE FOLLOWING PREPARATIONS FOR OPERATION BEFORE STARTING THE 

BE SURE TO MAKE THE FOLLOWING PREPARATIONS FOR OPERATION BEFORE STARTING THE 

STATION’S OPERATION:

STATION’S OPERATION:

The station may contain remnants of technical fluids after passing testing and configuration work.

Fig. 5

1.

 Check for fuel in the tank. The fuel level is displayed on the fuel level sensor on the 

control panel.

2. 

Check the oil level (fig. 5).

a) Remove the oil dipstick and wipe it clean.

b) Insert the dipstick.

c) Pull out again and check the oil level on the dipstick mark.

d) Oil level should be in the middle between the MAX and MIN labels.

3. 

Check the coolant level. Before starting the power plant for the first time, pour the 

coolant through the hole at the top of the plant (fig. 3, Item 4). Replace the coolant every 

2 years, unless otherwise specified in the fluid specification. If you have any questions, 

please contact an authorized representative of the manufacturer or an authorized dealer 

in your area.

4. 

Check the battery charge, if necessary, charge the battery tank with an external charger 

(not included), or let the power plant run for more than an hour at a load of at least 30% 

at the first start-up.

If the power plant is idle for a long time with the external power supply turned off, it is recommended to 

recharge the battery from an external charger every 3 months.

Diesel fuel type should correspond the operating season.

IMPORTANT!

If the station is in automatic mode at startup, the battery 

is recharged from the built-in the charger.

WARNING!

Each time you start the generator, be sure to check oil 

and fuel level.

IMPORTANT!

2

2

3

3

4

4

5

5

6

6

11

11

10

10

9

9

8

8

7

7

1

1

1. Next screen in the same group.  

LAMP TEST if held pressed
2. Fault condition indicators
3. Graphic LCD screen
4. Previous display group
5. Next display group
6. Previous screen in the same group. 

ALARM Mute

7. Mimic Diagram(sysem status)

8. STOP mode button

9. AUTO mode button

10. RUN mode button
11. TEST mode button

Содержание KS 18-1DE-G

Страница 1: ...Diesel power plant in noise absorbing housing Please read this manual before use Instruction KS 18 1XM KS 18 1YE KS 18 1DE G KS 25 3DE KS 33 3XM KS 33 3YE KS 33 3DE G EN...

Страница 2: ...from flammable liquids gases at a minimum distance of 1 m Install the generator at a distance of not less than 1 m from the front control panel and not less than 50 cm on each side including the uppe...

Страница 3: ...and one phase circuit breaker is prohibited ATTENTION DANGER The use of low grade fuel can lead to a degradation of the manufacturer s declared specifications or to engine failure Do not add any chemi...

Страница 4: ...ocated indoors take its exhaust outside The engine exhaust contains combustion products harmful to health ATTENTION DANGER It is necessary to take into account the restriction of access to the power p...

Страница 5: ...ectrician or an authorized dealer Power plant grounding is not a guaranteed protection against electric shock WARNING INDOOR POWER PLANT PLACEMENT CONDITIONS 2 1 FOUNDATION AND VIBRATION ISOLATION FOU...

Страница 6: ...ulate around the entire power plant When installing a diesel power plant outside the following must be provided Protection from natural factors such as rain snow ice precipitation with wind flood dire...

Страница 7: ...2 Fuel tank opening 3 Air filter 4 Fuel filter 5 Oil dipstick 6 The oil drain hole 7 Oil filling hole cover 8 Alternator 9 Exhaust pipe 10 Engine cooling radiator 11 Engine cooling fan 12 Anti vibrat...

Страница 8: ...Engine speed monitoring system mechanical mechanical electronic Engine heating equipped GENERAL CHARACTERISTICS Alternator model DPC184F DPC184F DPC184F Controller Datakom D 300 Fuel tank volume l 53...

Страница 9: ...2545 3170 3707 3168 Engine speed monitoring system mechanical mechanical mechanical mechanical Engine heating equipped GENERAL CHARACTERISTICS Alternator model DPC184E DPC184G DPC184G DPC184G Control...

Страница 10: ...start 4 Check the battery terminals for corrosion and clean them if necessary 5 Check the control panel and power plant for dust and dirt clean if necessary 7 Clear the space around the power plant o...

Страница 11: ...cation If you have any questions please contact an authorized representative of the manufacturer or an authorized dealer in your area 4 Check the battery charge if necessary charge the battery tank wi...

Страница 12: ...ups are made with and buttons Each depression of the button will cause the display to switch to the next group of parameters After the last group the display will switch to the first group Each depres...

Страница 13: ...ke sure that the rated power of power consumers matches with the power of generator Do not exceed the nominal power of the generator Do not connect the device before starting the engine If the power p...

Страница 14: ...hree or four attempts it may mean that the fuel tank is running out of fuel Check the fuel level in the tank according to the values on the indicator IMPORTANT USING OF THREE PHASE POWER PLANT MODEL U...

Страница 15: ...NUAL COMPLIANCE MANUAL COMPLIANCE Technical maintenance operation and K nner S hnen generator storage are to be performed according to this manual recommendations Manufacturer bears no responsibility...

Страница 16: ...g Fan and pump belt Valve gaps Flushing the cooling system and radiator Water separator Air cleaner element Radiator rank external Fuel tank Fan belt RECOMMENDED OILS 10 fill to here fill to here Moto...

Страница 17: ...t on flat level surface 2 Unscrew the oil gage cap on the engine fig 4 p 5 3 By means of a funnel pour the advanced purification engine oil to the crankcase fig 4 p 13 Oil level after filling has to b...

Страница 18: ...ing with the help of an external charger To avoid discharging the battery it is recommended to run the generator at least once a month for 30 minutes If the generator is not used for a long time pleas...

Страница 19: ...sel cannot be operated 6 If the external environment temperature is low use warm start up please 7 Check if the fuel pressure sensor is blocked Low battery voltage alarm LOW BATTERY VOLTAGE alarm ligh...