STATUS LEDS
STATUS LEDS
::
ALARM:
ALARM:
Turns on when a shutdown alarm or loaddump condition exists.
WARNING:
WARNING:
Turns on when a warning condition exists
SERVICE REQUEST:
SERVICE REQUEST:
Turns on when at least one of the service counters has expired.
MODE LEDS:
MODE LEDS:
Each led turns on when the related mode is selected, either locally or remotely.
MIMIC DIAGRAM LEDS:
MIMIC DIAGRAM LEDS:
MAINS AVAILABLE:
MAINS AVAILABLE: This led turns GREEN when all mains phase voltages and the mains frequency are
within limits. If enabled, the mains phase rotation order must be also right. When any digital input is
defined as Remote Start, this led will reflect the status of the input. When a Simulate Mains signal is
present, then mains status will become “available”. When a Force to Start signal is present, then the
mains status will become “not available”.
MAINS CONTACTOR ON:
MAINS CONTACTOR ON:
Turns on when the mains contactor is activated.
GENSET CONTACTOR ON:
GENSET CONTACTOR ON:
Turns on when the genset contactor is activated.
GENSET AVAILABLE:
GENSET AVAILABLE: This led turns on when all genset phase voltages and the genset frequency are
within limits. If enabled, the genset phase rotation order must be also right.
If a Remote START input is defined, then the MAINS led
will reflect the input status. Simulate MAINS and FORCE
to START signals will also affect this led.
WARNING!
STARTING TO WORK
8
Before starting the engine,
make sure that the rated power of power consumers matches with the
power of generator. Do not exceed the nominal power of the generator.
Do not connect the device
before starting the engine!
If the power plant is used as the main power source, the total long-term load must not exceed 80% of the
rated power of the station.
It is forbidden to load the power plant above the max.
power!
WARNING!
Do not connect the load to the power plant before start-
ing the engine and entering operating mode.
WARNING!
AUTOMATIC MODE
AUTOMATIC MODE
1. Press to activate the automatic power plant control mode. The LED indicator that lights up next to
the button indicates the selected control mode.
2. The power plant is controlled in a pre-programmed automatic mode. When the parameters of the
external electrical network deviate from the norm (increased or decreased voltage, increased or decreased
frequency, phase loss, incorrect phase sequence), the monitoring timer turns on and the display starts
counting down. If during this period of time, the parameters of the external electrical network are restored
to normal, the signal for automatic engine start is canceled.
3. After receiving the start signal, the start delay timer starts, preheating will occur - 10 seconds indicated
by the LED (optional function).
4. One second after that, the starter is triggered and the engine starts. If the engine does not start during
the start attempt, the starter takes a break of 10 seconds. Three consecutive engine start attempts occur
automatically.
In case of three unsuccessful attempts to start the en-
gine, the system notifies about the detected problem by
using indicator.
WARNING!