22
RFD TEHNICAL DESCRIPTION.doc
KON-215-60-33.2-v.1.0-E
High impedance restricted earth-fault protection of transformers
(ANSI 87N, IEC ∆I
0
>, REF)
- Measurement inputs
IEA, IEB
- Function activation
Func.
OFF
ON
-
task
interval
5 ms
- Source current input
Source
IEA
IEB
default: IEA
- Pickup value
dI
0
>
5
– 50 %
default: 20 %
Overcurrent protection with definite time characteristic (ANSI No. 50)
- Measurement inputs
IAA, IBA, ICA
- Function activation
Func.
OFF
I>
I>, I>>
I>, I>>, I>>>
- First/second/third stage
- Pickup value
I>, I>>, I>>>
0.00
– 30.00 In
step: 0.01 In
- Pickup time characteristic
Definite time
t>, t>>, t>>>
0.05
– 300.00 s
step: 0.01 s
- Allowed dropdown time
t-drop
0.00
– 60.00 s
step: 0.01 s
Cold Load Pickup
< 30 ms (at 2Ip)
- CLP first/second/third stage
- Pickup value
< 35 ms (at 2Ip)
- Pickup time characteristic
Definite time
0.95 (Ip/In ≥ 0,5)
- Start time
2% pickup value or 10 ms
- Release time
2% pickup value or 0.01 In
- Pickup/release ratio
- Time accuracy
- Pickup current accuracy
Overcurrent protection with inverse time characteristic (ANSI No. 51)
- Measurement inputs
IAA, IBA, ICA
- Function activation
Func.
OFF
ON
- Pickup value
I>
0.10
– 5.00 In
step: 0.01 In
- Pickup time characteristic
IEC-Normal inverse
k
0.05
– 1.00
step: 0.01
IEC-Very inverse
IEC-Extremely inverse
IEC-Long inverse
ANSI-Inverse
TD
0.50
– 15.00
step: 0.01
ANSI-Short inverse
ANSI-Long inverse
ANSI-Moderately inverse
ANSI-Very inverse
Содержание konpro
Страница 1: ......
Страница 2: ...2 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E...
Страница 6: ...6 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E Figure 3 Block scheme of the RFD relay...
Страница 36: ...36 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E MEASURMENT SCHEMATIC AND RELAY DIMENSIONS...
Страница 37: ...37 KON 215 60 33 2 v 1 0 E RFD TEHNICAL DESCRIPTION doc...
Страница 38: ......