21
KON-215-60-33.2-v.1.0-E
RFD TEHNICAL DESCRIPTION.doc
Protection functions
Stabilized three phase differential transformer protection (ANSI No. 87T)
- Measurement inputs
IAA, IBA, ICA
IAB, IBB, ICB
- Function activation
Func.
OFF
ON
-
task
interval
5 ms
- Pickup value
dI-basic
5
– 50 %
default: 20 %
- Pickup value
dI-start
10
– 50 %
default: 30 %
- Pickup value
TP2
100
– 300 %
default: 150 %
- 2. stage pickup value
dI>>
0.50
– 30.00 In
default: 1.00 In
- harmonic block function activation
HarmBLK
OFF
2nd
5th
2nd, 5th
- 2. harmonic pickup value
2nd BLK
7
– 20 %
default: 15 %
- 5. harmonic pickup value
5th BLK
10
– 50 %
default: 35 %
- maximum inrush current
Imax
1.00
– 20.00 In
default: 7.00 In
Stabilized low impedance restricted earth-fault protection of transformer primary
(ANSI No. 87TN-A)
- Measurement inputs
IAA, IBA, ICA, IEA
- Function activation
Func.
OFF
ON
-
task
interval
5 ms
- Pickup value
dI
0A
>
5
– 50 %
default: 20 %
- time delay
t>
0,00
– 300,00 s
default: 0,05 s
- blocking by inrush function activation
InRushBLK
OFF
ON
default: OFF
Stabilized low impedance restricted earth-fault protection of transformer secondary
(ANSI No. 87TN-B)
- Measurement inputs
IAB, IBB, ICB, IEB
- Function activation
Func.
OFF
ON
-
task
interval
5 ms
- Pickup value
dI
0A
>
5
– 50 %
default: 20 %
- time delay
t>
0,00
– 300,00 s
default: 0,05 s
- blocking by inrush function activation
InRushBLK
OFF
ON
default: OFF
Содержание konpro
Страница 1: ......
Страница 2: ...2 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E...
Страница 6: ...6 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E Figure 3 Block scheme of the RFD relay...
Страница 36: ...36 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E MEASURMENT SCHEMATIC AND RELAY DIMENSIONS...
Страница 37: ...37 KON 215 60 33 2 v 1 0 E RFD TEHNICAL DESCRIPTION doc...
Страница 38: ......