RFD TEHNICAL DESCRIPTION.doc                                                                                                                                  

KON-215-60-33.2-v.1.0-E

 

Other functions and parameters 

 

Time synchronization 

 

 

 

 

- Date 

Date 

[01 - 31] . [01 - 12] . 
[2000 - 2100]

 

Day. Month. 
Year 

 

 

 

 

- Time 

Time 

[00 - 23] . [00 - 59] . 
[00 - 59] 

Hour. Minute. 
Second. 

 

 

 

 

- Synchronization manner 

Sync. 

Internal 
IRIG-B 
Comm-103 
Bin. input 

 

 

 

 

 

- Time after synchronization termination 

T-sync. 

1 - 65535 

min 

 

Disturbance recorder 

 

 

 

 

- Function activation 
 

Func 

OFF 
ON 

 

 

 

 

 

- Sampling frequency 

Sampl. 

1KHz 
2KHz 

 

 

 

 

 

Prefault time

 

t-pre 

0.05 - 1.00 s 

step: 0.01s 

 

 

 

 

Postfault time

 

t-post 

0.05 - 1.00 s 

step: 0.01s 

 

 

 

 

Limit time

 

t-limit 

0.1 

– 5.0 s 

step: 0.1s 

 

 

 

 

- Trigger 

trigger: 
 

TRIP 
 PU 

 

 

CB Wear Monitoring

 

 

 

 

 

- Measurement inputs 

 

IA, IB, IC 

 

 

 

 

 

Function activation 

 

Func. 

OFF 
ON 

 

 

 

 

 

- Square current limit 

SumI^2 

0-1000000000 kA 

step: 1 

 

 

 

 

- Breaker opening time 

T-opening 

0,001-0,5 s 

step: 0,001s 

 

 

 

 

- Breaker breaking time 

T-breaking 

0,001-0,6 s 

step: 0,001s 

 

 

 

 

-  Current threshold 

Curr.thresh. 

0,04-1,00 In 

step: 0,01In 

 

 

 

 

- Measurement values 

 

 

 

Accumulated current value in phase A 

 IA 

0-2000000000 kA 

step: 1

 

Accumulated current value in phase B 

 IB 

0-2000000000 kA 

step: 1

 

Accumulated current value in phase C 

 IC 

0-2000000000 kA 

step: 1

 

Accumulated square current value in phase A 

 IA^2 

0-2000000000 

step: 1

 

Accumulated square current value in phase B 

 IB^2 

0-2000000000 

step: 1

 

Accumulated square current value in phase C 

 IC^2 

0-2000000000 

step: 1

 

Breaker trip counter 

Num of 
TRIPs 

0-2000000000 

step: 1

 

Manipulation counter 1A 

Oper.Count. 
1A 

0-2000000000 

step: 1

 

Manipulation counter 1B 

Oper.Count. 
1B 

0-2000000000 

step: 1

 

Manipulation counter 2A 

Oper.Count. 
2A 

0-2000000000 

step: 1

 

Manipulation counter 2B 

Oper.Count. 

0-2000000000 

step: 1

 

Содержание konpro

Страница 1: ......

Страница 2: ...2 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E...

Страница 3: ...ection The high degree of programmability derived from using the program matrix makes it easy to connect signals to digital inputs and relay outputs of the device The ability to create your own contro...

Страница 4: ...LCD front communication interface COM1 USB Remotely Rear optic interfaces COM0 service system COM2 service system Communication protocols IEC 60870 5 103 IEC 61850 Other functions Time synchronization...

Страница 5: ...is adapted for current inputs of 1A 5A and 0 2A for all device types For local communication with a computer we are using the standard USB interface For the realization of remote communication two op...

Страница 6: ...6 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E Figure 3 Block scheme of the RFD relay...

Страница 7: ...ansformer Protecting the power transformer with differential protection is complex because its rated current for HV and LV side are different amounts In addition in various groups of connections Trian...

Страница 8: ...d comparing measured values with preset ones Inter independent algorithms for each phase enable shortest failure detection time Three levels of settings for pickup current and time threshold allow sel...

Страница 9: ...n is used to detect failure conditions that can lead to damage of equipment powered by electric energy Those states can arise from e g phase interruption unsymmetrical phase load or absence of switchi...

Страница 10: ...of the signal switch If the chosen value is OFF the function deduces the state of the switch based on measured current through the switch If that current exceeds the parameter set by function Current...

Страница 11: ...nts can surpass nominal values by ten times As this is a brief transition event this state is not considered a failure The typical attribute of this state is the emersion of second harmonic inrush cur...

Страница 12: ...l is accepted as the international standard for protection parameter transfer and failure recording Figure 12 Communications connection schematic for facilities The figure 12 shows one kind of relay i...

Страница 13: ...13 KON 215 60 33 2 v 1 0 E RFD TEHNICAL DESCRIPTION doc Figure 13 Common connectivity schematic of basic relay types to measurement transformers with breaker state monitoring...

Страница 14: ...send a lot of signals as well In order to fulfil all potential demands relays allow expansion of circuitry with additional binary input and relay output expansion boards We offer three types of units...

Страница 15: ...15 KON 215 60 33 2 v 1 0 E RFD TEHNICAL DESCRIPTION doc Figure 15 Schematic of basic and additional relay modules...

Страница 16: ...diagram with the current state of the field apparatus showing all devices in the field Measured electrical values HMI interface is completely configurable by the user Since the switching devices chang...

Страница 17: ...nary inputs 18 80 Vdc 80 265 Vdc Analog inputs Additional card D type O I units 8 RTD inputs 2 analog inputs Measurement area of RTD input Measurement accuracy of RTD input 45 250 C 1 C Measurement ar...

Страница 18: ...COM 0 System Service interface COM 2 V Pin connector IEC 60870 5 103 V Pin connector IEC 60870 5 103 or 61850 Auxiliary power supply Auxiliary voltage 80 265 Vdc 18 80 Vdc 220 230V 50Hz Consumption St...

Страница 19: ...arge IEC 60255 22 2 IEC 61000 4 2 A1 A2 6kV by contact 8kV through air 4kV by contact 8kV through air Resistance to electromagnetic field radiation IEC 60255 22 3 IEC 61000 4 3 A1 A2 10V m 27 500MHz 8...

Страница 20: ...ilience testing According to standard IEC 60068 2 IEC 60255 6 Resilience to thermal influence in duration of 16 hrs IEC 60068 2 1 IEC 60068 2 2 25 C to 70 C Temporarily allowed installation temperatur...

Страница 21: ...ue 5th BLK 10 50 default 35 maximum inrush current Imax 1 00 20 00 In default 7 00 In Stabilized low impedance restricted earth fault protection of transformer primary ANSI No 87TN A Measurement input...

Страница 22: ...5 300 00 s step 0 01 s Allowed dropdown time t drop 0 00 60 00 s step 0 01 s Cold Load Pickup 30 ms at 2Ip CLP first second third stage Pickup value 35 ms at 2Ip Pickup time characteristic Definite ti...

Страница 23: ...step 0 01 s Allowed dropdown time t drop 0 00 60 00 s step 0 01 s Start time 35 ms Release time 35 ms Pickup release ratio 0 95 Ip In 0 5 Time accuracy 2 pickup value or 10 ms Pickup current accuracy...

Страница 24: ...o 0 95 Ip In 0 5 Time accuracy 2 pickup value or 10 ms Pickup current accuracy 2 pickup value or 0 01 In Secondary earthfault protection with inverse time characteristic ANSI No 51N B Measurement inpu...

Страница 25: ...In Working area all phase currents less than 4 In Negative sequence overcurrent protection with inverse time characteristic ANSI No 46 IT Function activation Func OFF ON Measurement inputs IAA IBA ICA...

Страница 26: ...unc OFF ON Alarm only Task interval 100 ms Time constant 1 Time const 1 1 999 min step 1min Time constant 2 Time const 2 1 999 min step 1min weight factor of time constant 1 p 0 00 1 00 step 0 01 Ambi...

Страница 27: ...et value or 10 ms Start criteria CB contact ON OFF Trip circuit supervision ANSI No 74TCS Function activation Func OFF A B A B Control current of trip circuit 5 mA Time delay t 0 10 3 00 s step 0 01 s...

Страница 28: ...000 kA step 1 Breaker opening time T opening 0 001 0 5 s step 0 001s Breaker breaking time T breaking 0 001 0 6 s step 0 001s Current threshold Curr thresh 0 04 1 00 In step 0 01In Measurement values...

Страница 29: ...9A Oper Count 9A 0 2000000000 step 1 Manipulation counter 9B Oper Count 9B 0 2000000000 step 1 Manipulation counter 10A Oper Count 10A 0 2000000000 step 1 Manipulation counter 10B Oper Count 10B 0 20...

Страница 30: ...ult 120 C location of RTD element no 5 Location5 None Other Oil Ambeint Winding Bearing default None pickup value of 1 Stage of term Input no 5 RTD5 St 1 0 250 C default 100 C pickup value of 2 Stage...

Страница 31: ...ent on side B CTB prim 1 2000 A default 100 A rated secondary current on side B CTB sec 1 A 5 A default 1 A rated primary current Io on side A CToA prim 1 2000 A default 100 A rated secondary current...

Страница 32: ...default 10 00 kV tap changer correction coefficient of primary side Tap1 0 50 2 00 default 1 00 tap changer correction coefficient of secondary side Tap2 0 50 2 00 default 1 00 Connection group HV HV...

Страница 33: ...IEA A AB Primary value of current IAB A BB Primary value of current IBB A CB Primary value of current ICB A EB Primary value of current IEB A SECONDARY VALUES AA Secondary value of current IAA A BA S...

Страница 34: ...3 1x FO IEC 60870 5 103 1x FO IEC 61850 BI R0 units 1 slot 0 No additional units A Binary unit A type 8BI 8RO B Binary unit B type 16BI C Binary unit C type 16RO D analog unit D type 7RTD 2AI BI R0 un...

Страница 35: ...characteristic IE 50N Earthfault protection with DT characteristic IE 50N Earthfault protection with DT characteristic IE 51N Earthfault protection with IDMT characteristic I2 46DT Negative sequence o...

Страница 36: ...36 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E MEASURMENT SCHEMATIC AND RELAY DIMENSIONS...

Страница 37: ...37 KON 215 60 33 2 v 1 0 E RFD TEHNICAL DESCRIPTION doc...

Страница 38: ......

Отзывы: