23
KON-215-60-33.2-v.1.0-E
RFD TEHNICAL DESCRIPTION.doc
ANSI-Extremely inverse
ANSI-Definite inverse
- Drop-out characteristic
Drop-out
Instant.
- Working area
1.10 Ip
- Release value
1.05 Ip (Ip/In ≥ 0,5)
- Pickup current accuracy
5% pickup value. ± 2%
current tolerance, 30 ms
- Time accuracy
2% pickup value or 0.01 In
Primary earthfault protection with definite time characteristic (ANSI No. 50N-A)
- Measurement input
IEA
- Function activation
Func.
OFF
IE>
IE>, IE>>
IE>, IE>>, IE>>>
- First/second/third stage
- Pickup value
IE>, IE>>, IE>>>
0.01
– 10.00 In
step: 0.01 In
- Pickup time characteristic
Definite time
tE>, tE>>, tE>>>
0.00
– 300.00 s
step: 0.01 s
- Allowed dropdown time
t-drop
0.00
– 60.00 s
step: 0.01 s
- Start time
< 35 ms
- Release time
< 35 ms
- Pickup/release ratio
0.95 (Ip/In ≥ 0,5)
- Time accuracy
2% pickup value or 10 ms
- Pickup current accuracy
2% pickup value or 0.01 In
Primary earthfault protection with inverse time characteristic (ANSI No. 51N-A)
- Measurement input
IEA
- Function activation
Func.
OFF
ON
- Pickup value
IE>
0.01
– 5.00 In
step: 0.01 In
- Pickup time characteristic
IEC-Normal inverse
kE
0.05
– 1.00
step: 0.01
IEC-Very inverse
IEC-Extremely inverse
IEC-Long inverse
ANSI-Inverse
TDE
0.50
– 15.00
step: 0.01
ANSI-Short inverse
ANSI-Long inverse
ANSI-Moderately inverse
ANSI-Very inverse
ANSI-Extremely inverse
ANSI-Definite inverse
- Drop-out characteristic
Drop-out
instant.
- Working area
1.10 Ip
- Pickup/release ratio
1.05 (Ip/In ≥ 0,5)
Содержание konpro
Страница 1: ......
Страница 2: ...2 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E...
Страница 6: ...6 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E Figure 3 Block scheme of the RFD relay...
Страница 36: ...36 RFD TEHNICAL DESCRIPTION doc KON 215 60 33 2 v 1 0 E MEASURMENT SCHEMATIC AND RELAY DIMENSIONS...
Страница 37: ...37 KON 215 60 33 2 v 1 0 E RFD TEHNICAL DESCRIPTION doc...
Страница 38: ......