37
UAB KOMFOVENT we reserve the right to make changes without prior notice
VERSO PRO2_2_20-02
Fig. 44.
Filter clamping device
To insert/remove filters, push two handles at the top and bottom of the filter forward to release a filter clamping device.
Filters are removed/inserted one by one (number of filters depends on the unit size). Once the filters are replaced/inserted,
handles are retracted and the filter clamping device presses the filters to the gaskets.
When inserting filters, make sure that their pockets are upright, filter frames are tightly seated and
gaskets are intact.
6. COMMISSIONING AND INSPECTION OF THE UNIT
Before switching on the device, check for foreign objects, debris or tools inside the unit. Make sure that air filters are
installed and condensate drainage is connected (if necessary), fill the siphon with water. Make sure that the ductwork is free
from obstructions such as fully closed diffusers or adjustment valves or blocked external air intake grilles.
•
You may start your AHU only when it is fully installed, ducts and external electrical elements are
connected. Do not start the unit without air ducts connected. This may distort air volume meas-
urements required for stable operation of the fans.
•
Do not use the unit with a temporary electrical power supply as unstable power can damage the
electronic components.