1.3.2. Counter-Flow Heat Exchanger (CF) Section
Due to heat exchange and condensation in counter-flow heat recovery units, heat exchangers may freeze at lower air
temperatures. To prevent freezing or to defrost, a heat exchanger is equipped with an air bypass damper or a multi-stage
damper system (according to the order). Formed condensate flows to condensate trays. If air velocity in the air handling unit
is high (> 2 m/s), an optional drop eliminator is installed, which prevents condensate from entering other parts of the unit
or air ducts. Recuperator section is also fitted with an automation box to which many of the main electrical components are
connected (see Chapter “Connection of Electrical Components”).
5
1
2
3
4
5
6 7
3.
4.
5.
8.
7.
6.
3.
Fig. 2.
Counter-flow heat exchanger (CF) section
1 – air bypass damper or a multi-stage damper system, 2 – automation box,
3 – counter-flow heat exchanger, 4 – drop eliminator,
5 – condensate trays, 6 – air bypass control board (C5_PM or C5_MDS),
7 – automatic switch, 8 – CF section label