5.2.5. Override function (OVR)
Selecting conditions for activating the function (all the time, only when the unit is running, only when the unit is stopped)
and specifying ventilation mode for the unit to run when the function starts. If the “Standby” ventilation mode is selected,
the unit will be stopped.
Enable
Override
Mode
All time
Comfort2
OVERRIDE FUNCTION (OVR)
5.2.6. Operation on demand (OOD)
Setting a critical air quality sensor value. The unit starts as soon as this value is exceeded.
Enable
Setpoint
OPERATION ON DEMAND (OOD)
800
ppm
5.2.7. Humidity control (HUM)
1
Setting a desired relative humidity level. Humidity level is set for two different ventilation modes during which this func-
tion will be used and the desired value will change automatically as the mode changes. If the unit operates in a different
ventilation mode than the one set, humidity control function is disabled automatically.
Enable
HUMIDITY CONTROL (HUM)
%RH
50
Setpoint 1
Mode 1
Comfort1
%RH
60
Setpoint 2
Mode 2
Comfort2
1
Displayed only when this function is pre-ordered.