NOTE: Read this entire instruction sheet before starting the installation.

  

     

        

I

MPORTANT 

C

ONSIDERATIONS

 

Improper  installation,  adjustment,  alteration,  service, 
maintenance,  or  use  can  cause  fire,  electrical  shock,  or 
other  conditions  which  may  cause  personal  injury  or 
property damage.  Consult your supplier or Steril-Aire for 
information or assistance.   
 
Understand  the  signal  words 

DANGER

WARNING

,  or 

CAUTION

.  These words are universally used for overall 

safety.   

DANGER 

identifies  the  most  serious  hazards 

which  will  result  in  severe  personal  injury  or  death.  

WARNING

  signifies  hazards  which  could  result  in 

personal  injury  or  death.   

CAUTION

  is  used  to  identify 

unsafe  practices  resulting  in  minor  personal  injury  or 
product and property damage.   
 

WARNING:    Before  performing  maintenance  or 

service  on  fixture,  ensure  unit  is  unplugged. 
Electrical shock can cause injury or death.  
 

CAUTIONS:

   

 

Never  expose  eyes  or  skin  to  UVC  light.  
Wear  gloves,  face  shield/glasses  (per  ANSI 
Z87.1) and cover all exposed skin.  

 

Do  not  touch  Emitter

 

glass  without  gloves.  

Damage  to  Emitter  may  result.    Oil  from 

fingerprints  will  permanently  etch  glass  of 
Emitter  and  weaken  structure.    If  necessary, 
clean  Emitter  using  a  Steril-Aire  cleaning  kit 
(isopropyl  alcohol  and  a  lint-free  wipe  may 
be substituted).   

 

Voltages  outside  of  the  range  designed  for 
the  unit  will  void  the  warranty  and  do 
permanent damage to the entire unit. 

  

 

Emitter contains a small quantity of mercury.  
If  an  Emitter  breaks,  clean  and  dispose  of 
with care.   

 

UVC  energy  may  cause  damage  to  non-
metallic components except for UV-rated and 
HVAC-style  drain  pans.    Select  mounting 
locations 

that 

prevent 

exposure 

to 

vulnerable 

components. 

 

If 

mounting 

locations are limited, such components shall 
be protected with UV resistant material such 
as  aluminum  foil,  aluminum  duct  tape, 
metallic shields, etc.  

 

The  qualified  installer  must  use  factory  kits 
and 

accessories 

when 

installing 

this 

product.

 

 

I

NSTALLATION 

&

 

O

PERATION

 

NOTE:    ENSURE  THAT  EMITTER  IS  INSTALLED  BEFORE 
POWER  IS  APPLIED.    INSTALLING  EMITTER  AFTER 
POWER  HAS  BEEN  APPLIED  WILL  TRIGGER  THE  “END-
OF-LAMP-

LIFE CIRCUIT” AND THE EMITTER MAY FAIL TO 

LIGHT.    IF  THIS  HAPPENS,  SHUT  OFF  POWER  FOR  10 
SECONDS AND THEN TURN POWER BACK ON.  EMITTER 
WILL THEN LIGHT. 

1.

 

Consult  all  applicable  codes  before  installing.  
Check  fixture  label(s)  for  the  correct  power 
requirements  and  supply  the  correct  voltage 

from a suitable, protected (fused), and grounded 
power source. 

2.  For  unitary  air  conditioners  and  smaller  air 

handler  units,  disconnect  power  from  unit.    For 
larger  units, 

the  Emitter  access  door  or  panel 

should  be  interlocked  with  the  power  source  to 
turn Emitter(s) off when the system is opened. It 
should  have  signs  (provided)  in  appropriate 
languages  alerting  maintenance  personnel  to 

Содержание Unitary Kit for Small Air Handlers

Страница 1: ...itter and weaken structure If necessary clean Emitter using a Steril Aire cleaning kit isopropyl alcohol and a lint free wipe may be substituted Voltages outside of the range designed for the unit will void the warranty and do permanent damage to the entire unit Emitter contains a small quantity of mercury If an Emitter breaks clean and dispose of with care UVC energy may cause damage to non metal...

Страница 2: ...cable can reach the pins of the Emitter and that its wires can reach the power source mount the power supply 3 50 2 08 1 54 3 88 Ø 14 6 INCH 4 PIN CIRCLINE SOCKET 10 INCH UP TO 24 INCH LAMPS 120V P N 40000121 INSULATED FEMALE 0 25 QUICK DISCONNECT 9 2 9 8 6 1 2 LONG POWER SUPPLY 120 TO 230 V 12 TO 42 LAMPS P N 10000166 1 6 32 LONG POWER IN 4 PIN CIRCLINE SOCKET 8 Based on the mounting option selec...

Страница 3: ... to accommodate component A and secure A with screws Slide Emitter partially through A Slide component B collared end first onto power supply s cord or extension cord and install cord onto Emitter pins see Photo 1 Slide Emitter and component B through A and twist and lock B under A s tabs see Photo 2 o U Bracket Connect the socket from the power supply to the Emitter Snap the Emitter s ceramic end...

Страница 4: ...ins Clean pins Reset Power System malfunction Check system components interlock door switches relays motion detectors etc Emitter reaching end of life Replace with new Emitter Reset Power Defective Power supply Replace Power Supply Low Radiometer Reading or Visibly Weak Emitter Light Dirty Emitter or Radiometer Clean Emitter Clean Radiometer lens Bad Wiring Check wiring to Emitter Emitter reaching...

Страница 5: ...Unitary Kit 22000100 RGTS 24 HO 24 Replacement Emitter for Unitary Kit 22000200 EMITTERS for Air Handler Kits GTS 12 VO 12 Replacement Emitter for Air Handler Kit 21000700 GTS 16 VO 16 Replacement Emitter for Air Handler Kit 21000100 GTS 20 VO 20 Replacement Emitter for Air Handler Kit 21000200 GTS 24 VO 24 Replacement Emitter for Air Handler Kit 21000300 GTS 30 VO 30 Replacement Emitter for Air H...

Отзывы: