UAB KOMFOVENT we reserve the right to make changes without prior notice
MOU_22-10
25
8.4.3. AHUKZ-02D
CN2 CN3 CN4 CN1
CN12
ENC1
SW1
SW2
SW3
SW4
SW9 SW10
ENC2 ENC3 ENC4
CN17 CN18
CN16
CN7
CN25
CN30
CN26
CN62
CN61
CN32
CN9
CN23
CN5
CN19
CN10
CN15
CN20
CN8
CN21
CN22
AHUKZ-02D CONTROLLER
OUTDOOR UNIT
L1 L2 L3 N
P Q E
L N
L1
L2
L3
N
GND
P
Q
E
XS1
XS3
XS5
XS7
XS9
TB2
T1
T2
T2A
TA
Temper
atur
e
sensors
AHU controller
board
EXV
XS11
3 x 400
VA
C
50/60 H
z
0..10V+ 0..10V -
COM
A
lar
m
D
efr
ost
Run
COM
Fan
Hea
t
Cool
ON/OFF
ENC1 settings
0
28 kW
MOU-280-HFN6
1
33,5 kW
MOU-335-HFN6
SW4 settings
SW4
ON
1 2 3 4
0..10 V capacity regulation
0-0.5 V 0% (outdoor unit stopped)
0.5-1.5 V, 10 % power
1.5-2.5 V, 20 % power
2.5-3.5 V, 30 % power
3.5-4.5 V, 40 % power
4.5-5.5 V, 50 % power
5.5-6.5 V, 60 % power
6.5-7.5 V, 70 % power
7.5-8.5 V, 80 % power
8.5-9.5 V, 90 % power
9.5-10.5V, 100% power
Содержание MOU Series
Страница 1: ...INSTALLATION MANUAL EN MOU ...