EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
MOU_22-10
24
COOL
– Digital input. When terminals are closed, the unit will run in cooling mode and “COOL” LED will
be on.
HEAT
– Digital input. When terminals are closed, the unit will run in heating mode and “HEAT” LED will
be on.
NOTE: HEAT signal has the priority. If both COOL and HEAT terminals are closed, unit will run in HEAT mode.
ENC1 (KA8140/KA8141)
– knob for multi split connection to select indoor unit capacity.
This knob is for multi indoor units connection only.
This knob will not work at one indoor to one outdoor connection.
Knob selection
Indoor unit capacity
Knob selection
Indoor unit capacity
0
2,0 kW unit
6
7,1 kW unit
1
2,6 kW unit
7
9,0 kW unit
2
3,2kW unit
8
10,5 kW unit
3
3,5 kW unit
9
14,0 kW unit
4
5,3 kW unit
A - F
16,0 kW unit
5
7,1 kW unit
ENC1 (KA8243/KA8245)
– knob to select condensing unit model.
Knob selection
Condensing unit
Knob selection
Condensing unit
0
5,3 kW unit
3
10,5 kW unit
1
7,1 kW unit
4
14,0 kW unit
2
9,0 kW unit
5
16,0 kW unit
LED lamps introduction:
RUN LED is lightened when controller is powered on.
HEAT LED is lightened when the unit is operating in heating mode.
COOL LED is lightened when the unit is operating in cooling mode.
DEF LED is lightened when the unit is in defrost mode.