EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
MOU_22-10
20
8.AHU KIT SPECIFICATIONS
8.1. Introduction
Control module enables to control inverter type outdoor unit without the needs of air conditioner
factory produced indoor unit. It gives possibility to control outdoor unit capacity and state to produce
heator cooling for AHU or water heater/cooler.
Control module enables to control inverter condensing unit capacity 0-10%~100% by external input
0~10VDC signal.
Dry contact signal is used to control outdoor unit to work in cooling or heating mode.
The installation and operation of outdoor unit as well controller must be done according to the manuals
(i.e. User’s manual, Installation manual, Technical Specification, Service Manual).
8.2. Specification and packing list
Model
KA8140/KA8141
KA8243/KA8245
AHUKZ-02D
Casing
Plastic
Plastic
Metal
Dimension (h × w × d)
61 × 100 × 191 mm
45 × 100 × 191 mm
125x345x393 mm
Weight
0.4 Kg
0.35 Kg
5.9 kg
Operation Temperature Range
-25 °C ~ +45 °C
-25°C ~ +45 °C
-25°C ~ +52°C
Operation Humidity Range
40 - 90 %
40-90 %
40-90 %
Power Supply
230 VAC, 1 Phase,
50/60Hz
230 VAC, 1 Phase,
50/60 Hz
230 VAC, 1 Phase,
50/60 Hz
Voltage Range
208 - 240V
208-240 V
208-240 V
Fuse
15 A, 250 V
15 A, 250 V
15 A, 250 V
Resistance class
IP54
IP54
IP 20
Packing list
Box body
1 piece
1 piece
1 piece
Box cover
1 piece
1 piece
1 piece
Anti-water seal
between box
body and box
cover
1 piece
1 piece
1 piece
Temp sensor
1 piece
1 piece (for KA8245 only)
5 pieces
Gland
3 pieces
3 pieces
4 pieces
Manual
1 piece
1 piece
1 piece
EXV valve with
pipes
-
-
1 piece
Control panel
-
-
1 piece
Cable
extension for
temperature
sensor
-
-
5 pieces
Cable
extension for
EXV valve
-
-
1 piece