EN
UAB AMALVA we reserve the right to make changes without prior notice.
54
“On”
– AQ function on.
“Off”
– function off.
After function is activated, the type of sensor, which is connected to the unit, is selected:
“VOC1”
(Volatile Organic Compound) – air quality sensor having signal-dependent linear relationship, the maxi-
mum value of output signal corresponds to the highest air quality.
“VOC2”
– air quality sensor having inverse relationship, the maximum value of output signal corresponds to
lowest air quality.
RH
– relative humidity sensor.
CO
2
– carbon dioxide sensor.
Depending on the sensor type, the value of AQ function is set, according to it the intensity of the unit is regulated.
If actual air quality value varies from the setpoint then ventilation intensity will increase otherwise – decrease.
For instance, if the humidity maintaining system is designed in the device, and there is additional relative
humidity (RH) sensor, then by setting 65% in the air quality window, and by regulating the intensity of ventilation
automatically, humidity of 65% will be maintained, i.e. if humidity increases, ventilation intensity will be increased
as well, and if humidity reduces, the device will switch back to the previous mode.
This function is not provided in the units with AC fans.
9. Season setting
For the air handling unit operating in most economical mode, summer and winter seasons have been provided.
•
By setting “Winter” season, unit cooling function is blocked.
•
By setting “Summer” season, unit heating function is blocked.
•
By setting “Auto”, automatic season selection will take place. Depending on the heating and cooling demand, the
season is selected automatically.
To set season select menu window:
Note:
If air temperature during summer season is insufficient, air handling unit can be preset and for “Winter”
season mode, its energy expenditures will be minimal.
10. Day and time setting
For the unit proper operation in automatic mode according to preset weekly schedule the day of the week and
time should be set:
Days notation:
Mo – Monday
Tu –Tuesday
We – Wednesday
Th – Thursday
Fr – Friday
Sa – Saturday
Su – Sunday
11. Weekly schedule setting
Two ways for weekly schedule setting have been projected:
• “1-5/6,7” – simplified schedule setting option: one schedule for all work days and the other for weekend operation;
•
“1-7” – weekly schedule setting option: different operation schedule for each day.
There is one operation schedule with two setting options.