7.5. Quick Ventilation Level Switchover
Three ventilation levels are projected in the unit. Each of them has its intensity (more detailed settings see in the
next chapter). There is possibility to switch ventilation level quickly from start-up window (7.3 Picture).
To increase ventilation intensity:
touch and hold
and at the same moment increase ventilation inten-
sity by touching
button.
To decrease ventilation intensity:
touch and hold
and at same moment decrease ventilation intensity
by touching
button.
If ventilation intensity is changed using quick switchover and unit is operating
according to weekly schedule, operation mode automatically is changed to
manual mode.
7.6. Unit Programmable Settings
By soft touching
button the parameters menu is entered. Menu window is selected by buttons
,
(see
further description). When menu window is selected, touch
for selecting desirable parameters and select the
value with
,
. To confirm the changes touch
.
To return to previous menu or to start-up window touch
button.
Note:
If touch sensitive buttons are inactive for 1 minute, start-up window is shown.
1. Unit operation modes setting
Two unit operation modes are possible: manual and automatic. In manual mode unit operates continuously by set
ventilation intensity. In automatic mode unit works according to weekly schedule (see further weekly schedule setting).
Note:
If automatic operating mode is selected, there is a symbol
in the start-up window.
2. Air volume control setting
Supply and exhaust air volumes control modes have been projected in the unit:
•
Constant air volume (CAV) control mode - unit supplies and exhausts constant air volume preset by the user, inde-
pendent of the processing changes in the ventilation system;
•
Variable air volume (VAV) control mode - unit supplies and exhausts air volume correspondingly to the ventilation
requirements in different premises. In case of frequently changing ventilation demands this air volumes mainte-
nance mode signally reduces unit exploitation costs.
Menu window for air volume control setting is provided only in the units having
air flow maintenance function. Only with EC fans.
If air handling unit is provided with variable air volume control function,
primary control mode calibration (look further) is essential, otherwise after
choosing VAV mode unit will not operate.
Variable air volume control mode calibration:
1. Before activating the device you should adjust air distribution and exhaust devices in ventilation system, open
all valves for variable air flow in a way enabling air supply to all ventilated premises.
2. Switch on the unit and by choosing menu window for air volume control setting (see above) actuate constant
air volume maintenance mode.
3. After choosing the CAV mode and being at the same menu window touch both
and
buttons at the
same moment. After this, calibration will start for 3 minutes and during this time unit will start working on maxi-
mum ventilation intensity and there will be displayed „Wait...“on the control panel. During calibration process
all buttons are inactive, except
which allows to shut down the unit and stop the calibration.
4. After finishing the calibration process, air handling unit further will operate in the previously settled mode.