6.4. Temperature Sensors Installation
Supply air temperature sensor B1 (6.4 a Picture) is mounted in the air duct in a projected place for it; after electric
heater or cooler section (if provided). The minimal distance from the air vent of the unit up to the sensor should be
not less than double diameter of the circular connection or a diagonal of rectangular connection.
Water temperature sensor B5 (6.4 b Picture) is mounted on the return water pipe by screwing it into the provided
hole. It is recommended that the sensor would be thermo insulated!
Supply air temperature sensor B1 Return water temperature sensor B5
6.4 a Picture
6.4 b Picture
6.5. Control Panel Installation
1. Control panel must be installed in the room under given following conditions:
1.1. ambient temperature range 0
0
C ... 40
0
C;
1.2. relative humidity limits 20 % … 80 %;
1.3. protection must be ensured from accidentally vertically falling water drops (IP X2).
2. Installation height must be not less than 0,6 m from the ground.
3. Control panel connection is projected through the hole in its backside.
4. Control panel is fixed after screwing two holes on the fastening surface.
Control panel is connected to the connection box terminals (see 6.3 a Picture) to the provided terminals (6.3 b
Picture). The length of the cable between the control panel and the unit should not exceed 150 m. Cable type is
specified in unit wiring diagram.
Control Panel Connection
When closing the panel window, do not bend the springs inside as this may
inhibit the functions of the panel buttons! Disconnect power supply prior to
connecting the control panel!
Control panel connection and other cable thicknesses are specified in the
wiring diagram!
6.5 Picture