TS_600_00 PW1000 1-3kVA User Manual 6/4/17
33
6
Troubleshooting
6.1
Introduction
If the UPS shuts down due to a fault condition, caused by an internal malfunction or severe overload, it might need to be
reset to bring it back into operation – see paragraph 6.6. Depending on the nature of the fault, the UPS may either shut
down entirely and disconnect the load supply or transfer the load to the internal bypass.
6.2
Fault identification
Unless there is a total UPS failure, the UPS will generally:
• illuminate the red
FAULT
LED
• display a Buzzer Code (error code) number on the LCD screen – the code indication may be steady or flashing
depending on other factors
• sound the audible warning alarm – the audible warning may be cancelled by pressing the
ON
button briefly
• illuminate the warning symbols at the top of the LCD screen if applicable
6.2.1 Error codes
6.2.2 Audible warning alarm
Figure 6.2 Audible warning alarm interpretation
Buzzer Codes
05
Weak or faulty battery
06
Output short-circuited
07
EPO Operated
11
UPS Over temperature
12
Inverter overload
14
Fan failure
28
Bypass overload
39
Low input voltage (<160V) or disconnected battery
Audible Alarm (beeps)
Continuous beep
UPS Faulty, Inverter shut down, keypad error, all functions inhibited
Single beep every two seconds
UPS Faulty, load continued to be supplied via inverter or bypass.
Single beep every second
UPS On-Battery mode, battery discharging
Quick and short successive beeps
Battery low, nearing end of discharge
Two quick and short beeps
Confirm / RS232 port receiving.
One quick and short beep
Service Mode OK
INPUT
UPS
LOAD
Alarm
Buzzer Code
1
2
Figure 6.1 LCD Fault Display (Fan failure example)