TS_600_00 PW1000 1-3kVA User Manual 6/4/17
19
3: Installation
The adjustable mounting rail kit contains a pair of mounting rails (left and right handed) that are fitted to each side of the
cabinet and secured by two screws – front and back. The length of the rails is adjustable between 543 mm and 925 mm,
making them compatible with most standard 19 inch rack assemblies of 600 mm to 900 mm depth.
1. Extend the adjustable mounting rail and hold in place (see Figure 3.6).
2. Align the two holes in the back of the adjustable mounting rail with the holes in the cabinet’s
vertical fixing rail (see Figure 3.7).
3. Identify and mark the two vertical fixing rail holes to which the adjustable mounting rail is to
be fixed.
4. Clip captive nuts (B5) to the two vertical fixing rails holes identified above.
5. Secure the rear of the adjustable mounting rail to the vertical fixing rail using two dome
headed bolts (B6).
6. With the rear of the adjustable mounting rail secured in place, and the adjustable mounting
rail extended, identify the four fixing points that will align with the equipment mounting
handles and clip four captive nuts to the required fixing points.
7. Secure the adjustable mounting rail to the rack’s front vertical fixing rail using two
countersunk bolts (B7) and adapter plate (B3) (see Figure 3.8)
.
8. Repeat the above steps to fit the second adjustable mounting rail.
Figure 3.8 2U Adjustable rail front mounting
9. When both mounting rails are fitted, carefully insert the UPS / Battery enclosure into the rack so that it rests correctly
on the rails. Then secure it in place using the four dome head bolts (B6) as shown in Figure 3.8
.
WARNING:
The UPS / Battery enclosure is heavy. When lifting the equipment ensure that adequate manpower
is available and any mechanical lifting aids are suitable for the weights involved.
WARNING:
When inserting the enclosure into the rack ensure that it is held level. If it is inserted at an angle it
could pivot about the back of the mounting rail runners if the front of the enclosure is tilted upwards.
B6
B2
Figure 3.7
B5
B3
B7
B6
Adjustable rail
Rack fixing rail
Adapter plate
B3