4: Operation
4.5.3 Functions menu
The Functions menu, shown in Figure 4.10, can be
accessed when the UPS is operating by pressing the
FUNCTION
button. The menu allows the operator to enable/
disable the buzzer, initiate a battery test and observe (but
not change) several UPS configuration set-up values.
Once the menu is open you can scroll down through the
screens by pressing the
DOWN
button, as shown.
Buzzer:
Allows the UPS buzzer to be enabled or disabled. This is
described in detail in paragraph 4.5.1.
Testing:
Initiates a battery test by switching the UPS to
ON
BATTERY
mode for 10 minutes and monitoring the battery
performance. This is described in detail in paragraph 4.5.2.
Bypass Voltage Window:
Displays the bypass voltage window setting. This shows the
acceptable bypass voltage range that can be connected to
the load when the UPS is operating
ON
BYPASS
and can be
either
Lo
(±15%)or
Hi
(±10%). This percentage relates to
the set inverter operating voltage – for example, if the
inverter voltage setting is 230V the bypass sensitivity
Lo
range is 230V ±15%, i.e., 195.5-264.5V.
Bypass Frequency Window:
Displays the bypass frequency window to which the inverter
will synchronise, which is either
1
[±1Hz] or
3
[±3Hz].
Inverter Voltage:
Displays the selected inverter output voltage setting, which
is either [200V], [208V], [220V], [230V] or [240V].
Mode:
Displays the selected UPS operating mode, which be either
Std
(standard) or
Eco
.
Inverter Voltage Adjustment:
Displays any applied output voltage offset adjustment,
which can be either [-3%], [-2%], [-1%], [0%], [+1%], [+2%]
or [+3%].
Buzzer
Testing
V
Inverter
Voltage
Hz
Bypass
Frequency Window
%
Inverter
Voltage Adjust
Mode
Bypass
Voltage
Window
Function
Figure 4.10 Functions menu