5. Make Electrical Connections – Latin America
NOTE:
The electrical rating of the product is printed on a label on the lumbar end of the bath.
All
vibracoustic baths are designed to operate between 110 V and 240 V at either 50 Hz or 60 Hz.
WARNING: Risk of electric shock.
Disconnect the power before performing the following
procedures.
WARNING: Risk of electric shock.
Connect the bath to a properly grounded Ground-Fault
Circuit-Interrupter (GFCI) or Residual Current Device (RCD) for protection against line-to-ground
shock hazard.
IMPORTANT!
The white wire should be connected to the load neutral terminal on the GFCI or RCD
breaker. The green wire is the
equipment ground
and must be connected to the neutral bus in the main
circuit breaker box.
Follow local electrical codes. Bond in accordance with national and local codes.
Remove the 120 V plug from the end of the electrical cord.
Remove the 120 V plug from the electrical cord on the junction box mounted to the control board.
Connect service to the amplifier with a 240 V plug (not included) or hardwire connection.
Connect service to the junction box with a 240 V plug (not included) or hardwire connection.
Control Power
Junction Box
Black (L1)
Wire Connector
Green (Ground)
From Control
White (Neutral)
Wire Connectors
Electrician to provide
suitable strain relief.
* Connections to be Made
at the Circuit Breaker
Typical 240 V Wiring Connection
Field Wiring
(From Junction Box
to GFCI Breaker)
* Equipment Ground
* Line Neutral
(White
Curly Wire)
Neutral Bus
(In Breaker Box)
240 V
240 V
Typical Single-Pole
Circuit Breaker
with GFCI
Breaker Box
L1
N
120/240 VAC Source
Bond in accordance with national and
local codes. Open bonding lugs are
located at the top of the junction box.
Load Neutral
1237790-2-D