5. Make Electrical Connections
WARNING: Risk of electric shock.
Disconnect the power before performing the following
procedures.
WARNING: Risk of electric shock.
Connect the pump motor, in-line heater, and blower/heated
surface to properly grounded, grounding-type receptacles protected by Ground-Fault
Circuit-Interrupters (GFCI’s) or Residual Current Devices (RCD’s). Do not remove the grounding
pins from the plugs. Do not use grounding adapters.
NOTICE:
The pump motor, in-line heater, and blower/heated surface are equipped with cords and plugs.
A qualified electrician must install two GFCI- or RCD-protected, 120 V, 20 A, grounded outlets for the
system. No other load should be on these circuits.
NOTE:
A label identifying the model number and electrical rating of the product is located near the
whirlpool pump.
Install two electrical outlets behind the bath, at least 1-1/2
″
(38 mm) above the subfloor, and within
24
″
(610 mm) of the power cords.
NOTE:
Make sure the air actuator tubing is securely attached to the pump and the blower, and is not
kinked or damaged.
Install the outlets at least
1-1/2" (38 mm) above the
subfloor, and within 24"
(610 mm) of the power cords.
Two GFCI-Protected
120 V, 20 A Grounded Outlets
Bath shown in alcove
for perspective.
In-line
Heater
Heated
Surface and
Blower
Whirlpool
Pump
Kohler Co.
9
1267113-2-C