8
TT-1574
1/12
LCM
Generator Set
COM
PWR
B
A
Connect one end of each cable shield
to GROUND at the generator set.
Leave one end of each cable shield disconnected at the last device.
PIM
1
COM
PWR
B
A
COM
PWR
B
A
Connect shields together
as shown.
1. Communication cable Belden #9402 or equivalent 20 AWG
shielded, twisted-pair cable
2. Engine start leads 3 and 4. See the ATS manual for cable
size specifications.
GND
A
B
COM
PWR
3
4
TB1
NOTES:
D
See the generator set Installation Manual for terminal
block location on generator set. Check the decal on
the generator set for terminal block connections.
D
See Figure 12 for maximum total cable length per run
(1 run shown)
D
Current transformer must be installed on the
emergency source leads.
RBUS
12 VDC
COM
PWR
A
B
ATS
Models RDT
or RSB
2
2
4
3
Figure 14
Connection Details with Model RDT or RSB Transfer Switch
Содержание GM77177-KP1-QS
Страница 15: ...TT 1574 1 12 15 Figure 28 Dimension Drawing Load Control Modules ADV 8198 A...
Страница 16: ...16 TT 1574 1 12 Figure 29 Schematic Diagram LCM with Pre wired Harness GM81638 Sheet 1...
Страница 17: ...TT 1574 1 12 17 Figure 30 Schematic Diagram LCM with Terminal Blocks for Customer Connection GM81638 Sheet 2...
Страница 18: ...18 TT 1574 1 12 Figure 31 Wiring Diagram LCM with Pre wired Harness GM81374 Sheet 1...
Страница 19: ...TT 1574 1 12 19 Figure 32 Wiring Diagram LCM with Terminal Blocks for Customer Connection GM81374 Sheet 2...