TT-1574
1/12
5
14. Connect 120 VAC to the terminal block labeled
120 VAC in the lower left corner of the LCM
enclosure. See Figure 6 and the wiring diagrams
in Section 7. The circuit must be protected by a 15
amp fuse or circuit breaker (not provided).
Note:
When servicing the LCM, be sure to
disconnect power to this circuit.
15. Install the LCM enclosure cover.
16. Check that the generator set is OFF.
17. Reconnect the generator set engine starting
battery, negative (--) lead last.
18. Reconnect utility power to the generator set.
19. Check the items in the prestart checklist in the
generator set Operation Manual. Then press the
RUN button to start the generator set.
20. Press the test button on the LCM and verify that the
load relays operate in the order expected. See
Section 5.
Note: Load A adds first and sheds last.
Figure 10
System Wiring Decal