Section 8 Reconnection
Section 8 Reconnection
8.1 Voltage Reconnection
Use the following voltage reconnection procedure to
change the voltage of 4- and 12-lead generator sets.
Frequency changes require voltage regulator
and
governor adjustments.
Refer to the following procedure and the connection
schematics. Follow the safety precautions at the front of
this manual and in the procedure text and observe
National Electrical Code (NEC) guidelines.
NOTICE
This generator set has been
rewired from its nameplate voltage
to
246242
NOTICE
Voltage reconnection.
Affix a notice to the generator set
after reconnecting the set to a voltage different from the
voltage on the nameplate. Order voltage reconnection
decal 246242 from an authorized service distributor/
dealer
.
Note: Equipment damage.
Verify that the voltage
ratings of the transfer switch, line circuit breakers,
and other accessories match the selected line
voltage.
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
WARNING
Disabling the generator set. Accidental starting can
cause severe injury or death.
Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (--) lead first. Reconnect the negative
(--) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
Hazardous voltage. Moving parts.
Will cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
DANGER
Grounding electrical equipment. Hazardous voltage will
cause severe injury or death.
Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.
Short circuits. Hazardous voltage/current will cause
severe injury or death.
Short circuits can cause bodily injury
and/or equipment damage
.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Содержание 12EFKOZD
Страница 2: ...TP 7045 3 18c 2...
Страница 8: ...TP 7045 3 18c 8 Safety Precautions and Instructions Notes...
Страница 12: ...TP 7045 3 18c 12 Section 2 Location Lifting and Mounting Notes...
Страница 24: ...TP 7045 3 18c 24 Section 4 Exhaust System Notes...
Страница 28: ...TP 7045 3 18c 28 Section 5 Fuel System Notes...
Страница 34: ...TP 7045 3 18c 34 Section 6 Electrical System Notes...
Страница 50: ...TP 7045 3 18c 50 Section 7 Installation Drawings Notes...
Страница 54: ...TP 7045 3 18c 54 Section 8 Reconnection Figure 8 3 Generator Reconnection ADV 5875F U...
Страница 81: ...TP 7045 3 18c 81...
Страница 82: ...TP 7045 3 18c 82...
Страница 83: ...TP 7045 3 18c 83...