Section 5 General Maintenance
1
tp6576
1. Dipstick
Figure 5-4
Dipstick Location
D
Check that oil level does not show a reading above
the FULL mark on oil dipstick or to the point of
overflow in reservoir above the FILL mark.
See
Figure 5-4.
D
Check the type of oil grade usage according to engine
startup operating temperatures. See Section 5.3.1,
Engine Oil Selections.
Note:
Use of multigrade oil above 0
°
C (32
°
F) will
increase oil consumption.
Disabling the generator set.
Accidental starting can
cause severe injury or death.
Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
WARNING
Servicing the fuel system. A flash fire can cause severe
injury or death.
Do not smoke or permit flames or sparks near
the fuel injection system, fuel line, fuel filter, fuel pump, or other
potential sources of spilled fuels or fuel vapors. Catch fuels in
an approved container when removing the fuel line or fuel
system.
5.3.3
Oil Level Check
The recommended oil is AGIP Sigma super TFE
multigrade 10W40 specification API CH-4/CF SL,
ACEA E4, E5, E7, B4. See Section 5.3.1, Engine Oil
Selections. Alternatively, we recommend using Mobil
Delvac 1 SHC 5W40 specification API CF ACEA E4,
B4,B3. Too high an oil level causes high oil consumption
and engine carbonizing.
The 1.4BEOR uses 1.2 L (1.3 qt.) of oil. Too low an oil
level damages the engine. This quantity must be strictly
respected.
1. Make sure the vehicle is on a level surface and the
power unit is stopped.
2. Make sure the power unit has come fully to a halt.
3. Wear special protective gloves and clothing for
maintenance operations.
4. Unlock with the supplied plastic key, the top and
front access panels on the power unit enclosure.
See Figure 5-5.
1
tp6576
1. Top access panel lock
2. Top access panel
3. Front access panel fastener
4. Front access panel
2
3
4
Figure 5-5
Power Unit Enclosure and Access Panel
Locations
5. Turn the Master Switch (see Figure 5-6) to the OFF
position.
Содержание 1.4BEOR-12V
Страница 1: ...Heavy Duty Truck Mobile Generator Sets Model 1 4BEOR 12V TP 6687 9 10a Operation...
Страница 4: ...TP 6687 9 10 4 Notes...
Страница 8: ...TP 6687 9 10 8 Safety Precautions and Instructions Notes...
Страница 10: ...TP 6687 9 10 10 Introduction Notes...
Страница 14: ...TP 6687 9 10 14 Section 2 General Description and Technical Data Notes...
Страница 20: ...TP 6687 9 10 20 Section 3 Operation and Use Notes...
Страница 30: ...TP 6687 9 10 30 Section 5 General Maintenance Notes...
Страница 36: ...TP 6687 9 10 36 Section 7 Operating Hours Notes...
Страница 40: ...TP 6687 9 10 40 Appendix Operating Hours Service Record Date Run Hours Run Total Hours Service Date Service...
Страница 41: ...TP 6687 9 10 41 Notes...
Страница 42: ...TP 6687 9 10 42 Notes...
Страница 43: ......