NUS-4
Seite 34
NUS-4 K05/0216
P85:
Cycle time for simulation (sec)
P86:
Simulated low level value (m)
P87:
Simulated high level value (m)
9.12 Access Lock
P99: dcba Access Lock by Secret Code
The purpose of this feature is to provide protection against accidental (or intentional) re-programming of
parameters.
The Secret Code can be any value other than
0000
. Setting a Secret Code will automatically be activated
when the NUS-4 is returned to the Measurement Mode. If the Secret Code is activated, the parameters
can only be viewed, this is indicated by the a flashing colon “:” between the parameter address and the
parameter value.
In order to program the device locked by a secret code, first enter the Secret Code in
P99
. The Secret
Code is re-activated each time the NUS-4 is returned to Measurement Mode.
To delete the Secret Code, enter the Secret Code in
P99
. After confirming it with
[E]
re-enter the
parameter
P99
and enter
0000
.
[dcba
(Secret Code)
]
[E]
[E]
[0000]
[E]
Secret Code deleted
10. Error Codes
Error
Code
Error description
Causes and solutions
1
Memory error
Contact local agent
No Echo
Echo loss
No echo received (no reflection)
See Action 5 and 6
3
Hardware error
Contact local agent
4
Display overflow
Check settings
5
Sensor error or improper
installation/mounting, level in the dead band
Verify sensor for correct operation and check for correct
mounting according to the User’s Manual
6
The measurement is at the reliability threshold Better location should be tried.
7
No signal received within the measuring range
specified in P04 and P05
Review programming, also look for installation mistake
12
Linearisation table error: both L(1) and L(2)
are zero
(no valid data-pairs)
See the Section ”Linearisation”
13
Linearisation table error: there are two same
L(i) data in the table
See the Section “Linearisation”
14
Linearisation table error: the r(i) values are not
monotone increasing
See the Section “Linearisation”
15
Linearisation table error: measured Level is
higher than the last Volume or Flow data-pair
See the Section “Linearisation”
16
The check sum of the program in the
EEPROM is wrong
Contact local agent
17
Parameter consistency failure
Check programming
18
Hardware failure
Contact local agent