NUS-4
Seite 16
NUS-4 K05/0216
Screens
Actions
APplication
xx
= select “EU” (European) for metric or “US” for US engineering units
(Use
UP
/
DOWN
keys)
yy= indicating “Li” for liquids
DEFAULT: EU
Programming of this parameter will result in loading the
factory default
with the corresponding engineering units.
H
=
xxxx maximum measuring distance
– Distance between transducer
face and tank bottom
Manual: set value
(
Use UP
/
DOWN
/
NEXT
keys)
and save it
(by
ENTER
E
)
Automatic: use the “GET LEVEL” function
(
UP
+
DOWN
)
to obtain
actual measured value with level in tank or a fixed target, i.e. wall. (“GET
LEVEL” functions only if ECHO LED is lit) and save it as above.
DEFAULT: maximum measuring distance [m], see Technical Data Table
4
mA
xxxx
–
level value
assigned to 4 mA current output
Manual: set level value
(by
UP
/
DOWN
/
NEXT
keys)
and save it
(by
ENTER
E
)
Automatic: use the “GET LEVEL” function
(
UP
+
DOWN
)
to display the
actual measured value with level in tank or a fixed target, i.e. wall. (“GET
LEVEL” functions only if ECHO LED is lit) and save it as above.
DEFAULT: 0 m (0%, Empty tank)
20
mA
xxxx
–
level value
assigned to 20 mA current output
Manual: set level value
(Use
UP
/
DOWN
/
NEXT
keys)
and save it
(by ENTER
E
)
Automatic: use the “GET LEVEL” function
(
UP
+
DOWN
)
to obtain
actual measured value with level in tank or a fixed target, i.e. wall. (“GET
LEVEL” functions only if ECHO LED is lit) and save it as above.
DEFAULT: max. level = max. measuring distance – dead band [m] (100%,
Full tank) (See Technical Data Table)
Error indication
by
the current output – select “Hold”, 3.8 mA or 22 mA (by
UP / DOWN key) and save it as above
.
DEFAULT: hold last value
damping time:
select required damping time
(
by
UP
/
DOWN
key
)
and
save it as above.
DEFAULT: 60 sec for liquids, 300 sec for solids
Note: – Current output can also be programmed for inverted operation: 4 mA=
100 % (Full), 20 mA= 0 % (Empty)
– Description of failures can be found under the chapter 10 Error codes.
H
:
xxxx
AP
:
xx
yy
4
:
xxxx
Er
:
xxxx
20
:
xxxx
dt
:
xxxx