Configuration Set NGM-HART
page 14
NGM-HART K05/0922
5.4.1
Threshold switching output
BASIC CONFIGURATION
• Read out actual lower / upper threshold switching output, by clicking on I13 and
I15.
Field G13/15 indicates the actual lower / upper switching threshold.
With the help of the thresholds, a hysteresis can be programmed to avoid output switching at
turbulent levels. First, the upper threshold must be passed to activate the output then the lower
threshold for deactivation of the output.
• Change actual lower / upper threshold in field G12 / G14 and click on I12 / I14
“set lower / upper threshold switching output mode”.
Verify changes by clicking again on I13 / I15 “get lower /
upper threshold switching output”