Configuration Set NGM-HART
page 10
NGM-HART K05/0922
5.2 Upper / Lower Range Value
BASIC CONFIGURATION
• Read out actual 4…20mA settings by clicking on I6 and I7
With the command “get lower / upper range value”, the actual 4…20 mA values in mm are shown
after the OK status disappeared and is visible again.
• Change actual 4…20 mA settings by changing the values in G4 and G5 and
clicking on I4 and I5 “set lower / upper range value”
• Verify changes by clicking again on I6 and I7 “get lower / upper range value”