4. Regulation Use 

Model DSS instruments monitor liquid flows. Only clean, homogeneous liquids of 
low  viscosity  -  against  which  the  instrument  materials  are  resistant  -  should  be 
monitored. Large switching inaccuracies may occur with highly viscous media. 
 
Large  dirt  particles  can  block  the  float  and  thus  cause  faulty  signals.  Pieces  of 
ferrite  deposited  on  the  embedded  float  magnet  can  also  cause  problems.  The 
installation of a magnetic filter is recommended to avoid these problems. 
 
The instruments are fitted as follows: 
 

Limit value contacts 

The instruments are fitted with one or two adjustable limit value contact(s) for flow 
rate monitoring. The contact can be adjusted over the entire measuring range by 
taking the hysteresis into consideration. 
 
 
 

5. Operating Principle 

 
The Flow Monitor model DSS works according to the well-
known variable area principle, however without the standard 
conical measuring tube that expands upwards. Instead the 
patented instruments have a cylindrical flow tube that is 
slotted conically along its length. A float is situated in this 
flow tube that is raised by the medium inflow. Each float 
level corresponds to a particular flow. Permanent magnets 
that activate the sealed contact (reed switch) arranged 
outside are embedded in the float. The contact is operated 
non-contacting by magnetic force, that is, the contact is 
separated hermetically from the flowing medium. 
 
 
 

 
 

Содержание DSS -11

Страница 1: ...Operating Instruction for Flow Monitor Model DSS...

Страница 2: ...ATEX reed contact 41R57 8 9 Commissioning 15 10 Maintenance 15 11 Technical Information 16 12 Order Codes 18 13 Dimensions 18 14 Recommended Spare Parts 19 15 EU Declaration of Conformance DSS 20 16 U...

Страница 3: ...age fee The devices are only to be used maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Health Safety and prevention...

Страница 4: ...djustable limit value contact s for flow rate monitoring The contact can be adjusted over the entire measuring range by taking the hysteresis into consideration 5 Operating Principle The Flow Monitor...

Страница 5: ...crew connections The instruments should not be installed in an induction field If possible check after mechanical installation that the threaded joint pipe connection is tight see section 9 Commission...

Страница 6: ...cting cable as shown in the wiring diagram If the contact has not been adjusted adjust it now see section 9 Commissioning Attention The specified electrical values for the sealed contact should not be...

Страница 7: ...DSS DSS K08 0322 Page 7 8 Use in hazardous area 8 1 Statement an apparatus not containing an own potential source following Directive 2014 34 EU...

Страница 8: ...x 250 VAC 1 5 A 100 VA 8 3 ATEX reed contact 41R57 ATEX N O contact 41R57 II 3G Ex ic IIC T4 Gc II 3 D Ex ic IIIC T125 C Dc 20 C Ta 80 C max 250 VAC DC 1 5 A 100 W 100 VA ATEX changeover contact 41R57...

Страница 9: ...eover contact The electrical connection is made via a plug only in intrinsically safe systems The reed switch is intended for commercial use and may only be used in accordance with the specifications...

Страница 10: ...rking 202 287 N O 70 75 with marking 202 288 Change over 60 65 change over contact 202 290 Change over 2 3 Temperature class The reed switch is suitable for temperature class T4 T125 C 2 4 General req...

Страница 11: ...he reed switch in conjunction with the individual evaluation devices functions properly and is approved for the intended use i The intrinsically safe connection including the reed switches must be mad...

Страница 12: ...of the reed switch o For the installation of the intrinsically safe circuit a control drawing system description to be created by the installer operator is required p Equipotential bonding must be est...

Страница 13: ...ich can only be obtained by using access devices such as a screwdriver e g steps if necessary and tools are visible For close up tests housing usually does not need to be opened or the equipment must...

Страница 14: ...rmed by specially trained and authorized personnel 6 Disposal Disposal of the packaging and used parts must be in accordance with the regulations of the country in which the product is installed 7 Mar...

Страница 15: ...oid pulsating flow as constant overranges due to pulsating flows which cause the float to strike against the float stop can lead to increased wear and tear and cause damage to the instruments In such...

Страница 16: ...ctor DIN EN 175301 803 Electrical switching values N O contact max 250 VAC DC 1 5 A 100 W 100 VA Changeover contact max 250 VAC DC 1 A 30 W 60 VA N O contact and changeover contact cCsAus max 230 VDC...

Страница 17: ...C Ta 80 C max 250 VAC DC 1 A 30 W 60 VA Hyteresis approx 3 5 mm float movement Protection IP 65 electr contact IP 54 side indicator Pressure loss Float material Measuring range l min water Pressure lo...

Страница 18: ...1109H DSS 1209H 2 14 DSS 1111H DSS 1211H 2 5 20 DSS 1113H DSS 1213H 3 45 DSS 1115H DSS 1215H R20 G 3 4 R25 G 1 N20 3 4 NPT N25 1 NPT 3 5 50 DSS 1117H DSS 1217H 10 110 DSS 1119H DSS 1219H R32 G 1 1 4...

Страница 19: ...he instrument models Specify instrument model when placing order 1 1 Float brass 3 2 O ring set FPM 1 2 Float polypropylene 4 1 Contact N O function 1 3 Float stainless steel 4 2 Contact changeover fu...

Страница 20: ...sive atmospheres Part 18 Equipment protection by encapsulation m EN IEC 63000 2018 Technical documentation for the assessment of electrical and electronic products with respect to the restriction of h...

Страница 21: ...eral requirements BS EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP Code BS EN IEC 63000 2018 Technical documentation for the assessment of electrical and electronic products wi...

Страница 22: ...DSS Page 22 DSS K08 0322 17 EU Declaration of Conformance reed contact 41R57 ATEX not available in GB...

Страница 23: ...DSS DSS K08 0322 Page 23 18 Statement of conformity reed contact 41R57 ATEX not available in GB...

Страница 24: ...DSS Page 24 DSS K08 0322 ATEX not available in GB...

Страница 25: ...DSS DSS K08 0322 Page 25 ATEX not available in GB...

Страница 26: ...DSS Page 26 DSS K08 0322 ATEX not available in GB...

Страница 27: ...DSS DSS K08 0322 Page 27 19 Declaration of the Manufacturer F0 ATEX not available in GB...

Страница 28: ...DSS Page 28 DSS K08 0322 20 EC Type Examination Certificate Magnetic reed switch F0 ATEX not available in GB...

Страница 29: ...DSS DSS K08 0322 Page 29 ATEX not available in GB...

Страница 30: ...DSS Page 30 DSS K08 0322 ATEX not available in GB...

Страница 31: ...DSS DSS K08 0322 Page 31 21 IECEx certificate F0 ATEX not available in GB...

Страница 32: ...DSS Page 32 DSS K08 0322 ATEX not available in GB...

Страница 33: ...DSS DSS K08 0322 Page 33 ATEX not available in GB...

Страница 34: ...DSS Page 34 DSS K08 0322 ATEX not available in GB...

Страница 35: ...DSS DSS K08 0322 Page 35 ATEX not available in GB...

Страница 36: ...DSS Page 36 DSS K08 0322 ATEX not available in GB...

Отзывы: