Sets the 'Constant Light Control Enable' object behavior after a power failure of the Bus
After recovering the bus can be enabled or not to consult the state of this object.
Origin of light sensor
Is necessary to select if the light sensor is internal (
•
External
: Enables the object 'External sensor value' in order to receive the value of an external
addition, it must selected whether the set point is parameterized by the ETS ('Origin of Requested lux level = Via ETS
parameter’) or via the communication object
communication object').
In case of choosing the parameterization by ETS,
Requested' parameter. Can be set values
•
Built-in
: four new parameters will be enabled in Advanced Settings
•
It is necessary to measure with a light meter in the sensor
o
At night only with lamps (lux):
and the lamps regulated to obtain the desi
o
At max. external light and lamps regulated to have requested level (lux):
sensor (ceiling) to the maximum value of daylight and the
lighting in the workplace
•
The adjustment of the lamps
o
At night only with lamps (%):
o
At max. external light and lamps regulated to have requested level (%):
with maximum daylight and lamps to the desired level
Constant light control
Allows conditioning the constant light control to the motion detection or to a communication object:
•
Only when movement detected: T
present, the system will send an OFF (or wh
•
Always: the constant light control
turning-on or turning-off of the lights can be made
•
Depending object mode value: in case of
'Permanent Constant light control', which
Enable Object for manual dimming
Allows enabling the dimming and manual switching from an external sensor (
Enabled Object:
Constant light object number
Allows to control several lighting lines (up to 4) with an adjustable percentage of increase:
attenuation’.
Enabled Object:
SPAIN)
mail:
– Web:
www.dinuy.com
Sets the 'Constant Light Control Enable' object behavior after a power failure of the Bus.
After recovering the bus can be enabled or not to consult the state of this object.
Is necessary to select if the light sensor is internal (built-in sensor) or external (a separate sensor):
Enables the object 'External sensor value' in order to receive the value of an external
whether the set point is parameterized by the ETS ('Origin of Requested lux level = Via ETS
) or via the communication object ‘Lux Level Requested’ ('Origin of Requested lux level = Via
he parameterization by ETS, it must entered the value of lux to keep through 'Lux Level
Can be set values between 100 lux and 1200 lux, in steps of 100
four new parameters will be enabled in Advanced Settings (
access to these settings only if really necessary)
It is necessary to measure with a light meter in the sensor:
At night only with lamps (lux): lighting value measured in the sensor (ceiling) without daylight contribution
regulated to obtain the desired lighting in workplace.
At max. external light and lamps regulated to have requested level (lux): lighting value measured in the
) to the maximum value of daylight and the lamps regulated to obtain the desired value of
kplace.
lamps is:
At night only with lamps (%): light level at which the lamps are regulated at night with
At max. external light and lamps regulated to have requested level (%): level at which
maximum daylight and lamps to the desired level.
Allows conditioning the constant light control to the motion detection or to a communication object:
The dimming will become operational only when motion is detected
present, the system will send an OFF (or whatever programmed) through the Bus after the set time delay ('Lag time')
control will operate every time, regardless of whether or not presence of people
of the lights can be made by a higher-level object.
n case of selecting this option is enabled other communication object No. 10
t Constant light control', which allows to control remotely the system commissioning
and manual switching from an external sensor (pushbutton, switch,.
Allows to control several lighting lines (up to 4) with an adjustable percentage of increase: ‘2nd constant light object
9
) or external (a separate sensor):
Enables the object 'External sensor value' in order to receive the value of an external light sensor. In
whether the set point is parameterized by the ETS ('Origin of Requested lux level = Via ETS
('Origin of Requested lux level = Via
the value of lux to keep through 'Lux Level
between 100 lux and 1200 lux, in steps of 100.
these settings only if really necessary)
:
alue measured in the sensor (ceiling) without daylight contribution
ighting value measured in the
regulated to obtain the desired value of
are regulated at night with only the lamps only.
evel at which lamps are regulated
Allows conditioning the constant light control to the motion detection or to a communication object:
will become operational only when motion is detected. If people is not
us after the set time delay ('Lag time').
time, regardless of whether or not presence of people. The
is enabled other communication object No. 10
remotely the system commissioning.
pushbutton, switch,...).
‘2nd constant light object