background image

KMD-5575 

Installation and Operation Guide

Important Notices

©2008 KMC Controls

The KMC logo is a trademark of KMC Controls, Inc. All rights reserved.

No part of this publication may be reproduced, transmitted, transcribed, 

stored in a retrieval system, or translated into any language in any form by 

any means without the written permission of KMC Controls, Inc. Printed in 

U.S.A.

Disclaimer

The material in this document is provided for information purposes only. The 

contents and the product(s) described herein are subject to change without 

notice. KMC Controls, Inc. makes no representations or warranties with 

respect to this document. In no event shall KMC Controls, Inc. be liable for 

any damages, direct or incidental, arising out of or related to the use of this 

document.

KMC Controls

P.O. Box 497

19476 Industrial Drive

New Paris, IN  46553

U.S.A.

TEL: 574.831.5250

FAX: 574.831.5252

E-mail:  [email protected]

Introduction

The KMC KMD-5575 Network Repeater-Isolator extends and reconditions 

EIA-485 network communications as well as enabling “T” or branch networks. 

The KMD-5575 is designed to recondition a degraded EIA-485 (formerly RS-485) 

communication signal on a KMC KMDigital or BACnet subnetwork. Two primary 

factors that cause communication signal degradation within the digital subnet

-

work are long subnetwork wiring lengths and the number of digital controllers 

connected to the subnetwork.

A KMD-5575 is required after every 31 consecutive controllers on KMDigital or 

BACnet subnetworks (e.g., between controllers 31 and 32) or if the cumulative 

wiring distance exceeds 4,000 feet. (For smoke control applications, the maximum 

total length of the EIA-485 network cable, including all repeaters, is 4,000 feet.)

In addition, the KMD-5575 is required for “T” or branch network wiring configu

-

rations (see Illustration 4 ).

Illustration 1 shows the major module components and their connections.

Illustration 1—Components

Status LEDs

Network 2
Connections

Network 1
Connections
Power
Connection

EOL Terminations

Circuit Ground

Repeater

KMD-5575

STATUS

2

1

 

EOL

A

B

GND

EOL

A

B

NETWORK-2

NETWORK-1

24 VAC

NETWORK-1 & 2

Installation

Mounting

Fasten the KMC KMD-5575 securely to a flat surface inside a metal enclosure 

using #6 hardware in the four mounting holes on the top and bottom (see Illustra

-

tion 2). For HVAC applications, KMC Controls recommends using a UL Listed 

enclosed energy management equipment panel such as a KMC model HCO-1034, 

HCO-1035, or HCO-1036. The HCO-1102 enclosure will hold one KMD-5575.

For smoke control applications, the controller must be mounted in a UL Listed 

Firefighter’s Smoke Control Station enclosure or listed enclosure with minimum 

dimensions. The minimum enclosure size is 16 x 18 x 6 inches. KMC enclosures 

HCO-1034, HCO-1035, and HCO-1036 are approved for this application. See 

Smoke Control Manuals 000-035-08 (BACnet) and/or 000-035-09 (KMDigital).

To maintain RF emission specifications, use either shielded connecting cables or 

enclose all cables in conduit.

Содержание KMD-5575

Страница 1: ... Operation Guide KMD 5575 Network Repeater Isolator 873 019 02D Contents Introduction 3 Installation 3 Mounting 3 Wiring and Terminal Blocks 4 Network Connections 4 Configuration EOL 7 Power Connection 7 Indicators and Operation 8 Accessories 8 Specifications 8 ...

Страница 2: ...ols Inc Printed in U S A Disclaimer The material in this document is provided for information purposes only The contents and the product s described herein are subject to change without notice KMC Controls Inc makes no representations or warranties with respect to this document In no event shall KMC Controls Inc be liable for any damages direct or incidental arising out of or related to the use of...

Страница 3: ...tration 1 shows the major module components and their connections Illustration 1 Components Status LEDs Network 2 Connections Network 1 Connections Power Connection EOL Terminations Circuit Ground Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Installation Mounting Fasten the KMC KMD 5575 securely to a flat surface inside a metal enclosure using 6 hardware ...

Страница 4: ...ower Limited Network Connections The KMD 5575 Network Repeater Isolator is designed to operate between net work segments Each network is connected to the respective terminals on the module See Illustration 1 Connect the shields of the cable together at each device on that segment Connect the shields to an earth ground only at one end of the segment Do NOT connect the cable shield to the circuit se...

Страница 5: ...segment Illustration 4 Repeater in a single T or Branch Sublan Configuration 24 VAC A T or Branch B Segment Y A Previous Controller B on Segment X A Next Controller B on Segment X EOL Jumper Removed EOL Jumper Installed Shield Grounded Shields Connected Shields should be connected to an earth ground at only one end of the segment Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1...

Страница 6: ...one end of the segment Other Segment X Controllers Other Segment X Controllers Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Shields Connected EOL Jumper Removed EOL Jumper Installed...

Страница 7: ...ace a KMC KMD 5567 surge suppressor in the cable run where it exits a build ing For smoke control applications the maximum total length of the MS TP network cable including all repeaters is 4 000 feet The MS TP communications network is supervised in smoke control applications and the ground fault impedance value for the circuit is 0 ohms For specific information on smoke control systems see Smoke...

Страница 8: ...15 20 60 Hz 3 VA Class 2 only NOTE All circuits including supply voltage are power limited AC power is non supervised in smoke control applications Baud Rate 9 600 to 38 400 Connections Removable screw terminal blocks wire size 14 22 AWG Network Wiring Belden 82760 or equivalent shielded twisted 18 AWG 5 5 ohms per 1 000 feet and 51 pF foot network connections are supervised in smoke control appli...

Отзывы: