KMD-5575 

Installation and Operation Guide

Illustration 3—Repeater at End of Line Between Two Network Segments

EOL Jumpers Installed

A     
B     

A    
B      

24 VAC

Shields Not Connected

Repeater

KMD-5575

STATUS

2

1

 

EOL

A

B

GND

EOL

A

B

NETWORK-2

NETWORK-1

24 VAC

NETWORK-1 & 2

Shield Grounded at One End*

Segment Y

Segment X

*Shields should be 

connected to an earth 

ground at only one 

end of the segment

Segment Y

Segment X

Other

Controllers

Other

Controllers

Illustration 4 shows a repeater connected in a single “T” or branch network con

-

figuration. (One branch is shown coming off a segment.)

Illustration 4—Repeater in a single “T” or Branch Sublan Configuration

~

24 VAC

A    “T” or Branch
B    Segment Y

A     Previous Controller
B     on Segment X

A     Next Controller
B     on Segment X

EOL Jumper
  Removed

EOL Jumper
   Installed

Shield Grounded*

Shields Connected

*

Shields should be connected to an earth 

ground at only one end of the segment

Repeater

KMD-5575

STATUS

2

1

 

EOL

A

B

GND

EOL

A

B

NETWORK-2

NETWORK-1

24 VAC

NETWORK-1 & 2

Repeater

KMD-5575

STATUS

2

1

 

EOL

A

B

GND

EOL

A

B

NETWORK-2

NETWORK-1

24 VAC

NETWORK-1 & 2

From Other

Controllers

To Other

Controllers

Segment Y

Segment X

Illustration 3 shows a repeater as it might appear connected between two network 

segments at the End-of-Line (EOL) position. (See the Configuration/EOL section 

for information about the EOL jumper.)

Содержание KMD-5575

Страница 1: ... Operation Guide KMD 5575 Network Repeater Isolator 873 019 02D Contents Introduction 3 Installation 3 Mounting 3 Wiring and Terminal Blocks 4 Network Connections 4 Configuration EOL 7 Power Connection 7 Indicators and Operation 8 Accessories 8 Specifications 8 ...

Страница 2: ...ols Inc Printed in U S A Disclaimer The material in this document is provided for information purposes only The contents and the product s described herein are subject to change without notice KMC Controls Inc makes no representations or warranties with respect to this document In no event shall KMC Controls Inc be liable for any damages direct or incidental arising out of or related to the use of...

Страница 3: ...tration 1 shows the major module components and their connections Illustration 1 Components Status LEDs Network 2 Connections Network 1 Connections Power Connection EOL Terminations Circuit Ground Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Installation Mounting Fasten the KMC KMD 5575 securely to a flat surface inside a metal enclosure using 6 hardware ...

Страница 4: ...ower Limited Network Connections The KMD 5575 Network Repeater Isolator is designed to operate between net work segments Each network is connected to the respective terminals on the module See Illustration 1 Connect the shields of the cable together at each device on that segment Connect the shields to an earth ground only at one end of the segment Do NOT connect the cable shield to the circuit se...

Страница 5: ...segment Illustration 4 Repeater in a single T or Branch Sublan Configuration 24 VAC A T or Branch B Segment Y A Previous Controller B on Segment X A Next Controller B on Segment X EOL Jumper Removed EOL Jumper Installed Shield Grounded Shields Connected Shields should be connected to an earth ground at only one end of the segment Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1...

Страница 6: ...one end of the segment Other Segment X Controllers Other Segment X Controllers Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Shields Connected EOL Jumper Removed EOL Jumper Installed...

Страница 7: ...ace a KMC KMD 5567 surge suppressor in the cable run where it exits a build ing For smoke control applications the maximum total length of the MS TP network cable including all repeaters is 4 000 feet The MS TP communications network is supervised in smoke control applications and the ground fault impedance value for the circuit is 0 ohms For specific information on smoke control systems see Smoke...

Страница 8: ...15 20 60 Hz 3 VA Class 2 only NOTE All circuits including supply voltage are power limited AC power is non supervised in smoke control applications Baud Rate 9 600 to 38 400 Connections Removable screw terminal blocks wire size 14 22 AWG Network Wiring Belden 82760 or equivalent shielded twisted 18 AWG 5 5 ohms per 1 000 feet and 51 pF foot network connections are supervised in smoke control appli...

Отзывы: