5
Network cable and rough-in preparation
Connecting a NetSensor to a controller requires a six-wire cable with
RJ-12 connectors on each end. KMC plenum-rated preassembled
cables are recommended. Cables made to length must meet the
following requirements:
◆
Cable length must be no longer than 75 feet (22.9 meters).
◆
Cable conductors must be no smaller than #24 AWG.
◆
Cable insulation must meet local building codes.
◆
Connectors must be appropriate for the cable in use and are
installed following the connector manufacturers instructions.
Complete rough-in wiring at each sensor location prior to sensor
installation. This includes the following:
◆
Routing the network cable from the NetSensor to a controller. See
.
◆
If required, install the appropriate backplate. See
for model numbers.
Caution
To prevent mounting screw heads from touching the circuit
board in the NetSensor, use only the mounting screws
supplied by KMC Controls. Using screws other than the
type supplied will damage the NetSensor.
Cable details
RJ-12