BAC-1xx36/1xxx36 Series (3 Relays and 6 Analog Outputs) Section
47
Application Guide L
Bills of Materials (BAC-1xx36/1xxx36)
AHU (Air Handling Unit)—Multiple H/C Options
BILL OF MATERIALS: AHU, 1 Heat and 1 Cool
REFERENCE
KMC PART #
PART DESCRIPTION
FLEXSTAT
BAC-1xx36/
1xxx36
BACNET THERMOSTAT, 6 RELAY & 3 ANALOG OUTPUTS
R1
REE-3211
MULTI-VOLTAGE CONTROL RELAY, 1.2 VA
HUMV
VEB-43xxxBDL
FAIL-SAFE CONTROL VALVE, W/ MEP-5372 2-10 VDC
ACTUATOR, 19 VA
FOR VALVE, CHOOSE CAPACITY/MODEL FROM KMC DATA SHEET
HUM
REE-3112
12/24 VDC CONTROL RELAY, SPDT
DAT
STE-1402
DUCT TEMPERATURE SENSOR
FST
CSE-1102
AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
MAT
STE-1416
12' DUCT AVERAGING TEMP SENSOR
OAT
STE-1451
OUTSIDE TEMPERATURE SENSOR
*
STE-6011
REMOTE TEMPERATURE SENSOR, TYPE II
*
SAE-10xx
REMOTE CO
2
SENSOR, SPACE OR DUCT
TX1
XEE-6311-050
TRANSFORMER, 120/240/277/480:24 VAC, 50 VA
CHOOSE ONE OF THE FOLLOWING TRANSFORMERS:
TX2
XEE-6311-075
TRANSFORMER, 120/208/240/480:24 VAC, 75 VA
TX2
XEE-6311-100
TRANSFORMER, 120/240/277/480:24 VAC, 96 VA
*The remote temperature and CO
2
sensor options are not shown in the sample installation
diagrams, and they are available only on BAC-12xxxx/13xxxx/14xxxx models.
BILL OF MATERIALS: AHU, DAMPER ACTUATORS
REFERENCE
MAX DAMPER
AREA IN FT
2
KMC PART #
PART DESCRIPTION
OAD or RTD
6.25
MEP-5372
50 IN·LB FAIL-SAFE ACTUATOR, 2-10VDC,
19VA
OAD or RTD
15
MEP-7252
120 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
25VA
OAD or RTD
22.5
MEP-7552
180 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
25VA
OAD or RTD
40
MEP-7852
320 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
40VA
NOTE: See the corresponding
BAC-1xx36
or
BAC-1xxx36
Installation Guide section for detailed drawings and input/
output connections as well as other important installation
information.
NOTE: Remote temperature and CO
2
sensors are available only on
BAC-12xxxx/13xxxx/14xxxx models. When IN7 is configured
for a remote space temperature sensor, space temperature can
be configured for onboard, remote, averaging of the two, the
lowest reading, or the highest reading. When DCV is enabled
in the BAC-1
2
xxxx (without a built-in CO
2
sensor), IN9 is
assumed to be connected to an external SAE-10xx CO
2
sensor.
BAC-13xxxx/14xxxx FlexStats also have the external CO
2
sensor
option, and if used, the highest of the two readings (internal
vs. external) will be used to control DCV sequences. See the
FlexStat Operation Guide
for more details.
NOTE: Humidity and motion/occupancy sensor options are dependent
on FlexStat model.
NOTE: See also
Sequence of Operation (BAC-1xx36/1xxx36) on page 50
.
NOTE: Do not use REE-3211 relays with
analog
outputs! See
Connecting Outputs on page 7
.