FlexStat (General)
20
Application Guide, Rev L
Resetting Hospitality Mode Setpoints to Defaults
Hospitality Setpoint Principles
In Hospitality mode, users have continuing control over single, occu-
pied, and unoccupied setpoints:
• Under the Single Setpoint option, the setpoint will remain at what-
ever value was last selected by a user until a user adjusts the setpoint
again.
• Under the Schedule option, the setpoint values persist even after
switching between scheduled occupied and unoccupied periods.
For example, if a user changes the occupied cooling setpoint to 76°,
the occupied cooling setpoint will remain at 76° on subsequent days
until a user adjusts it again.
To automatically reset setpoints to default values at particular times (e.g,
daily near midnight):
• A building automation system can overwrite the setpoint value ob-
jects. See
Custom Web Graphics on page 17
as well as the Control Basic
program section below to determine values to control.
• Custom programming can be put into the FlexStat. See the Control
Basic program section below and
Custom Programming on page 8
.
Control Basic Programs
For the
Schedule
option, add an equivalent of the following Control
Basic lines:
REM Reset Hospitality Mode Setpoints to Schedule
Defaults
IF
+
TIME
> 23:59:00
THEN GOSUB
RESET_SETPOINTS
REM 23:59:00 = 11:59 PM
END
RESET_SETPOINTS :
AV4@8 = 78 :
REM UNOCC COOLING SETPT
AV4.RELINQUISH_DEFAULT = AV4
AV5@8 = 66 :
REM UNOCC HEATING SETPT
AV5.RELINQUISH_DEFAULT = AV5
AV20@8 = 74 :
REM OCC COOLING SETPT
AV20.RELINQUISH_DEFAULT = AV20
AV21@8 = 70 :
REM OCC HEATING SETPT
AV21.RELINQUISH_DEFAULT = AV21
RETURN
For the
Single Setpoint
option, use this instead:
REM Reset Hospitality Mode Setpoint to Schedule De-
fault
IF
+
TIME
> 23:59:00
THEN GOSUB
RESET_SETPOINT
REM 23:59:00 = 11:59 PM
REM AV27 = UI Setpoint; BV7 = Heat/Cool Mode
END
RESET_SETPOINT :
IF
BV7
THEN
REM COOLING MODE
AV27@8 = 74
ELSE
REM HEATING MODE
AV27@8 = 70
ENDIF
AV27.RELINQUISH_DEFAULT = AV27
RETURN