FlexStat (General)
25
Application Guide, Rev L
Remote Sensors (Wired in Parallel)
Connected to a FlexStat Input
FlexStat
Obstr
uction
Obstr
uction
Adding Remote Motion Sensors
Situations that would need remote sensors to be connected to the Flex-
Stat include:
• Areas too large for adequate coverage by the FlexStat’s built-in sensor.
• Areas with obstructions that block sensor coverage.
• Use of FlexStat models that do not have a built-in sensor.
Remote motion sensors can be connected to one of the FlexStat’s avail-
able inputs. (Custom programming is required.) Multiple remote sen-
sors with dry (relay/switch) contacts can be wired in parallel to monitor
a variety of different zones.
An example Control Basic program (for BACstage or TotalControl) that
turns occupancy override on from remote sensors is:
IF AI2 < 1 THEN START BV40 : REM START EXTERNAL OCC
SNSR BV IF INPUT IS SHORTED
IF AI2 > 1 THEN STOP BV40 : REM STOP EXTERNAL OCC
SNSR BV IF INPUT IS OPEN
IF BV40 AND NOT BV1 THEN START BV2 : REM IF EXTER-
NAL OCC SNSR BV IS ACTIVATED AND FLEXSTAT IS NOT
IN OCC, START OVRD MODE
NOTE: The application must have one unused input. Input #2 is used
in this example and assumes Normally Open relays/switches
in the remote sensors. In such a case, the input pull-up resistors
should be set to 10K ohms, and SNSR2 in the Application menu
must be set to NOT USED.
NOTE: To trigger the occupancy override, the remote sensor
contacts
must stay closed for two seconds or longer.
SYSTEM
SYSTEM ENABLE: AUTO
OCC OVRIDE (HRS):
INACTIVITY (SECS): 60
DISPLAY BLANKING: NO
0.5
NOTE: All Schedules must
be deleted or set to
OFF.
MOTION SENSOR
OCC OVERRIDE:
STATE: OCCUPIED
STANDBY: DISABLE
ENABLE
SCHEDULE
ENTIRE WEEK [MON–SUN]
WEEKDAYS [MON–FRI]
WEEKEND [SAT–SUN]
INDIVIDUAL DAYS
HOLIDAYS
ENTIRE WEEK
1: 12:00:00 AM
2:
3:
4:
5:
6:
[—>] DELETES ENTRY
OFF
NOTE: Motion Sensor Occupancy
Override must be enabled and
Standby should be disabled.
NOTE: System Occupancy Override
time should usually be re-
duced to 0.5 hours in the Sys-
tem menu. Alternately reduce
the time to less than 0.5 hours
using BACstage or TotalCon-
trol to change AV16’s present
value and relinquish default.
USER INTERFACE
MODE: HOSPITALITY
ROTATION VALUES
SHOW TEMP TENTHS: NO
HOSPITALITY OPTIONS
SETPT CNTRL:
SCHEDULE
NOTE: For Hospitality Mode,
Setpoint Control must be set
to Schedule.
Menu Configuration
SENSOR SETUP
IN 2:
IN 9: NOT USED
SPACE TEMP: ONBOARD
-- IN 1 IS ONBOARD
NOT USED
NOTE: If IN2 or IN9 is used for the
input, configure it as “Not
Used” in the Sensor Setup
menu.
NOTE: See the
FlexStat
Operation Guide
for
more information on
these menus.