FlexStat (General)
19
Application Guide, Rev L
Reverting UI Modes
Via the User Interface
Reverting to Standard mode can be done through the FlexStat’s user
interface with a combination of button presses or by changing MSV9’s
values through BACstage or TotalControl.
To revert to Standard mode
through the user interface
, follow these steps to access the hidden
menus:
1. Press and hold both the
Enter
and
Right
buttons for at least five sec-
onds. (If you push the
Right
button before
Enter
while in Hospitality
mode, you will go to the Field B screen.)
2. While continuing to hold those two buttons, press the
Left
button and
hold all three buttons for at least five seconds.
3. Release the
Right
button but continue holding the
Left
and
Enter
but-
tons until the FlexStat menu appears (after about five more seconds).
NOTE: While holding the
Left
,
Right
, and/or
Enter
buttons, do not
accidentally also hold the
Up
or
Down
button.
NOTE: The FlexStat menu has
view-only
About, Date, and Time
lines. The About selection contains the same information as
the About screen in the Standard mode’s Main Menu. The
Date and Time lines simply display the current date and time
information.
4. To
access and make changes in the “hidden” Main Menu
, use the
Up
/
Down
buttons to navigate to the
SECOND
blank line below the
Time line and press the
Enter
button.
NOTE: Access to this hidden menu is password protected (if both the
Operator and Administrator passwords are not 0000). Entering
either an Operator or Administrator level password accesses
the Main menu (a User password will not work).
5. The menus operate as normal from this point.
To return to Standard
mode, navigate to the Advanced > User Interface menu and select
Standard (otherwise, the previously selected mode will continue).
Via BACstage or TotalControl
To revert to Standard mode through BACstage or TotalControl:
1. Change the Present Value of MSV
9
from 2 (HOSPITALITY in
TotalControl) or 3 (LOCKED UI) to 1 (STANDARD).
NOTE: When the FlexStat is restarted, however, MSV9’s Present
Value will revert to the Relinquished Default and the user
interface will revert to the previously selected mode.
If a
quick configuration change is desired instead of a permanent
mode change, this is a helpful tool.
2. To make the change
permanent, change the Present Value AND the
Relinquished Default to the desired value.
NOTE: Do not change the Present Values or Relinquished Defaults
of any other MSVs 1–12. Doing so may make the FlexStat
malfunction!