Pressure Independent VAV Applications with CEP/CSP-4000 Series
43
CTE-5202 Applications Guide, AN0912A Rev. D
Pressure Independent
This section gives sample applications for using the
CTE-5202 as a substitute for the CTE-1000 series
thermostats with the CEP/CSP-4000 series VAV
controller-actuators. (See also the
4xxx with the CSP-4702, see
or CSP-40xx/42xx/44xx/46xx on page 21
.)
The C
E
P-4000 series uses SS
E
-1000/2000 series flow
(“hot wire anemometer”) sensors. These sensors
consists of two coils of wire mounted in the air
stream: one monitors airflow, while the other is a
reference used for duct temperature compensation.
These sensors also include a temperature sensor for
use with heating/cooling “changeover” applications
(which requires an additional relay module).
The C
S
P-4000 series uses SS
S
-1000 series differential
air flow sensors or a pitot tube instead of the SSE-
1000/2000s. Otherwise wiring is the same as with the
CEP-4000 series used in these examples.
To
manually drive
the controller/damper
open
or closed
(with 24 VAC on terminals 9 and 10),
remove the wiring
to terminal 6, and
temporarily jumper
terminal 6 to:
•
Terminal 5 (9.1 VDC) = Open
•
Terminal 4 (– VDC) =
Closed
NOTE: Full
rotation
may take five to six
minutes because the
actuator rotates at 18° per
minute.
VAV and CAV Applications
with CEP/CSP-4000 Series
CAUTION
Do not short terminals 12 and 14, 4 and 5, or 2
and 4.
NOTE: Concerning replacements of the CTE-1x1x
thermostats, see
NOTE: The old CSP-40xx/42xx/44xx/46xx models
are very different from the new CSP-4702.
Pressure Independent VAV Applications
CEP-4xxx
24 VAC
CTE-5202
Damper
SSE-1000 Series Sensor
SET
POINT
7
6
5
4
3
2
1
8
9
10
11
12
13
14