General Information (All Applications)
8
CTE-5202 Applications Guide, AN0912A Rev. D
Cross-References
Thermostat Replaced
CTE-5202
Sequence
Selected
Example
Replacement
Applications
KMC /
Nailor /
Dynacon*
Anemostat
(East/West)*
Metal
Industries*
Metalaire*
Nailor*
ASC /
Titus*
13-27,
004100
10027401
#1
#3 (disregard cooling
setpoint) or #1 (with
8K–10K ohm resistor for
RA mode)
13-29
01EC-2146
B3-3001-
015 or
B3-015
#3
13-28
01EC-2129 THM1004
10027403
#2
THM1005
#1 (setback used for night
setpoint)
#1 (setback used for day
setpoint)
004643
THM1101
10027415
#1
01EC-9229 THM1103
10027411
#1 (single duct) or #3
(dual duct)
THM1105
10027413
#1
#1 (setback used for day
setpoint)
*NOTE: CTE-1x0x thermostats require a power supply of
9.1 VDC
, typically supplied by a CEP/CSP-4xxx controller/actuator, and they
have a 0–6 VDC output range. The CTE-5202 can also operate on the 9.1 VDC power supplied by CEP/CSP-4xxx controller-actuators,
but the CTE-5202’s outputs will be reduced to a maximum of about 5.3 VDC (or a maximum of about 2000 fpm from the CEP/CSP-
4xxx). In almost all such applications, this is adequate. In a rare application that requires a full 6 VDC output (or 3000 fpm maximum
from the CEP/CSP-4xxx), the CTE-5202 can be powered by the 24 VAC transformer, which can be easily done by switching the wire
from Terminal #5 (+9.1 VDC) to Terminal #10 (24 VAC, phase) on the CEP/CSP-4xxx. See
9.1 VDC vs. 24 VAC Power Options on page
. See also the
CEP-4000 Series Applications Guide
.
Barber Colman (TAC, Invensys, Schneider Electric)
Thermostat Replaced
CTE-5202 Sequence Selected
TP-8101, TP-8102, and TP-8103
#1
TP-8124 and TP-8125
#3
For wiring and sample applications, see
Barber Colman TP-81xx Thermostats Replacement Applications on page 54
.