Single-Zone Heating and Cooling Applications
14
CTE-5202 Applications Guide, AN0912A Rev. D
Chilled Beam 4-Pipe Heating and Cooling
~
T
T
AI1
AO
1
AO
2
CTE-5202
Thermostat
24 VAC
~
–
(Phase)
(Neutral)
24 V
A
C
Common
Input
Cooling Valve
24 V
A
C
Common
Input
Heating Valve
Select Sequence 3
AO2 MAX
AO2 MIN
AO2 (RA)
AO1 (DA)
AO1 MIN
AO1 MAX
Cooling
Setpoint
Heating
Setpoint
Temp.
Increasing
2° F
2° F
This application enables both heating and cooling
in a chilled beam and baseboard or equivalent
installation.
This works for NC 2–10 and 0–10 VDC valves or NO
10–2 and 10–0 VDC valves.
Select Sequence
3
from the CTE-5202
SYSTEM