Single-Zone Heating and Cooling Applications
13
CTE-5202 Applications Guide, AN0912A Rev. D
Chilled Beam Cooling
~
T
T
AI1
AO
1
AO
2
CTE-5202
Thermostat
24 VAC
~
–
(Phase)
(Neutral)
24 V
A
C
Common
Input
Valve
Select Sequence 1
This application controls cooling in a chilled beam or
equivalent installation.
This works for NC 2–10 and 0–10 VDC valves or NO
10–2 and 10–0 VDC valves.
Select Sequence
1
(from the CTE-5202
SYSTEM
Change Configuration on page 6
Cooling Max.
Cooling Min.
Setpoint
(
Colder
Room Temperature
Warmer
)