CTE-5202 Analog Electronic Thermostat w/ LCD Display 

Applications Guide, AN0912A Rev. D

Applications Guide

DRAFT

NOTE: W

atermark is on non-

writable DRAFT W

atermark 

layer

. Turn the layer off or 

delete layer to remove from 

the final document.

CTE-5202

Analog Electronic Thermostat w/ LCD Display

Contents

General Information (All Applications) .................................................................................. 3

Important Notices ..........................................................................................................................................................4
Accessories ....................................................................................................................................................................4
Connection and Configuration .......................................................................................................................................5

Connections ...............................................................................................................................................................5
External Input (AI1) ....................................................................................................................................................5
Change Setpoint .........................................................................................................................................................6
Change Configuration ................................................................................................................................................6
Sequences ..................................................................................................................................................................7

Cross-References ............................................................................................................................................................8
CTE-5202 Troubleshooting ...........................................................................................................................................10

Display Is Blank ........................................................................................................................................................10
Setpoint Is Not Maintained ......................................................................................................................................10
Temperature Reading Is Incorrect ............................................................................................................................10
Wiring Issues ............................................................................................................................................................10

Single-Zone Proportional Heating and Cooling Applications ............................................... 11

Heating, RA and DA .....................................................................................................................................................12
Chilled Beam Cooling ..................................................................................................................................................13
Chilled Beam 4-Pipe Heating and Cooling ...................................................................................................................14
Chilled Beam 2-Pipe Heating and Cooling with Changeover ........................................................................................15

Pressure Dependent VAV Applications with MEP-4xx2 ........................................................ 16

Cooling or Heating .......................................................................................................................................................17
Auto and Override (to Fully Closed) ............................................................................................................................18
Other Applications .......................................................................................................................................................18

Содержание CTE-5202

Страница 1: ...Change Configuration 6 Sequences 7 Cross References 8 CTE 5202 Troubleshooting 10 Display Is Blank 10 Setpoint Is Not Maintained 10 Temperature Reading Is Incorrect 10 Wiring Issues 10 Single Zone Proportional Heating and Cooling Applications 11 Heating RA and DA 12 Chilled Beam Cooling 13 Chilled Beam 4 Pipe Heating and Cooling 14 Chilled Beam 2 Pipe Heating and Cooling with Changeover 15 Pressur...

Страница 2: ...Reheat and Night Setback Setup 36 Cooling with Heating Changeover 37 Cooling with Heating Changeover and Electric Reheat 38 Cooling with Heating Changeover and Hot Water Reheat 39 Cooling with Hot Water Reheat 40 Fan Induction with 2 Stage Electric Heat 41 Dual Duct Minimum Air from Cold Duct 42 Pressure Independent VAV and CAV Applications with CEP CSP 4000 Series 43 9 1 VDC vs 24 VAC Power Optio...

Страница 3: ...ces troubleshoot ing and other related information For general mounting and connection details including power connections and input output connections see the CTE 5202 Installation Guide For specifications and other information see the CTE 5202 Data Sheet The latest support files are always available on the KMC Controls web site www kmccontrols com Shown adjusting the Cooling setpoint during norm...

Страница 4: ...is for information purposes only The contents and the product it de scribes are subject to change without notice KMC Controls Inc makes no representations or warran ties with respect to this document In no event shall KMC Controls Inc be liable for any damages direct or incidental arising out of or related to the use of this document Accessories HMO 1161 Wall plate al lows mounting to horizontal 2...

Страница 5: ...uence which causes the cooling setpoint in all Sequences to increase and the heating setpoint in Sequence 2 or 3 to decrease by the amount of the setback offset This setback does not apply during the morning warm up se quence See for example Cooling with 3 Stage Reheat and Night Setback Setup on page 25 and Cooling with 3 Stage Reheat and Night Setback Setup on page 36 Connections Standard connect...

Страница 6: ...ns to change the desired values If no Auxiliary Flow is desired set AO1 AUX to 0 To change any of the system or advanced features press the Up or Down button until the desired flash ing ADVANCE or SYSTEM menu appears and then press the Setpoint button The ADVANCE menu enables changing via the Up Down buttons the values of DEAD BD Deadband or minimum setpoint differential adjustable from 1 to 10 F ...

Страница 7: ... AO1 MIN HOT AIR SEQUENCE Morning Warm Up AO1 RA AO1 MAX AO1 MAX AO1 MIN Temp Increasing 6 Volts Setpoint 2 F Of Loop 10 2 F 2 F AO1 MIN AO1 MAX AO1 MAX AO1 RA HOT AIR SEQUENCE Morning Warm Up AUX AO1 MIN COLD AIR SEQUENCE AO1 DA AO2 RA 0 Volts 12 Volts SEQUENCE 2 Single Duct Cooling with Reheat and Auxiliary Flow AO2 Disabled 0 Volts Temp Increasing Cooling Setpoint Heating Setpoint Heating Setpo...

Страница 8: ... 1x0x thermostats require a power supply of 9 1 VDC typically supplied by a CEP CSP 4xxx controller actuator and they have a 0 6 VDC output range The CTE 5202 can also operate on the 9 1 VDC power supplied by CEP CSP 4xxx controller actuators but the CTE 5202 s outputs will be reduced to a maximum of about 5 3 VDC or a maximum of about 2000 fpm from the CEP CSP 4xxx In almost all such applications...

Страница 9: ...roller to use an unlimited signal Limits for the CTE 5202 and AO1 and AO2 would then be left at the default 0 and 12 KMC CTE 50xx Thermostat Replaced CTE 5202 Sequence Selected Example Replacement Applications CTE 5001 5011 1 See page 45 and page 48 9 1 VDC CTE 5002 5012 2 See page 47 9 1 VDC CTE 5003 5013 No Replacement 9 1 VDC CTE 5006 5016 2 See page 35 16 VDC CTE 5015 1 See page 33 16 VDC NOTE...

Страница 10: ...oint during very cold weather adjust the setback in the ADVANCE menu See Change Configura tion on page 6 If space temperature is overshooting the setpoint or oscillating try increasing the proportional band by a degree in the ADVANCE menu If the problem persists try increasing the integral value slightly up to 20 If the problem still persists try setting the integral value to 0 The optimal integra...

Страница 11: ...ection gives sample applications for using the CTE 5202 in single zone proportional heating baseboard heaters and cooling chilled beams with valves or SCR control NOTE For chilled beam applications separate control of humidity is required to prevent condensation T T AI1 AO1 AO2 CTE 5202 Thermostat Return From Coil To Coil Supply 24 VAC Common Input Valve ...

Страница 12: ...figuration on page 6 The resistor simulates a changeover sensor and puts the thermostat in Re verse Acting mode NOTE If the resistor value is too high the thermostat will not go into RA mode If the resistor value is too low the thermostat may go into setback mode This RA control works for NO 2 10 and 0 10 VDC valves or NC 10 2 and 10 0 VDC valves as well as equivalent SCR controls For Direct Actin...

Страница 13: ...hase Neutral 24 VAC Common Input Valve Select Sequence 1 This application controls cooling in a chilled beam or equivalent installation This works for NC 2 10 and 0 10 VDC valves or NO 10 2 and 10 0 VDC valves Select Sequence 1 from the CTE 5202 SYSTEM menu See Change Configuration on page 6 Cooling Max Cooling Min Setpoint Colder Room Temperature Warmer ...

Страница 14: ... 24 VAC Common Input Heating Valve Select Sequence 3 AO2 MAX AO2 MIN AO2 RA AO1 DA AO1 MIN AO1 MAX Cooling Setpoint Heating Setpoint Temp Increasing 2 F 2 F This application enables both heating and cooling in a chilled beam and baseboard or equivalent installation This works for NC 2 10 and 0 10 VDC valves or NO 10 2 and 10 0 VDC valves Select Sequence 3 from the CTE 5202 SYSTEM menu See Change C...

Страница 15: ...ype III temperature sensor provides the CTE 5202 an automatic change over for heating cooling applications using hot and chilled water The sensor will switch the thermostat between cooling and heating modes based on the temperature of the water in the pipe A water temperature higher than changeover temperature switches control to heating mode and a temperature lower than changeover temperature swi...

Страница 16: ...VAV applications The MEP 4xx2 s default direction is CCW to close CW to open or CW with increasing voltage but this can be reversed by a switch during installation and configuration See also the MEP 4000 Series Installation Guide For additional applications see Pressure Indepen dent VAV Applications with CSP 5001 5002 on page 32 and make the corresponding wiring adjustments for power to the MEP 4x...

Страница 17: ... actuator See the MEP 4000 Series Installation Guide For cooling select Sequence 1 from the CTE 5202 SYSTEM menu See Change Configuration on page 6 Heating Air Heating Max Heating Min 1650 fpm 0 fpm Setpoint Colder Room Temperature Warmer 3300 fpm Cooling Max Cooling Min 1650 fpm 0 fpm Setpoint Colder Room Temperature Warmer 3300 fpm AO1 Signal Cooling Air AO1 Signal Select Sequence 1 Select Seque...

Страница 18: ... Only NC SPST Relay Override to Fully Closed MEP 4002 Actuator 24 VAC Common Input Out Auto and Override to Fully Closed Adding a Normally Closed SPST relay or switch enables overriding the air flow to fully closed Otherwise the example below is the same as the configuration in Cooling or Heating on page 17 The default setting is Auto When the NC relay energizes the thermostat signal is removed fr...

Страница 19: ...and connections to the SSS 100x air flow sensors NOTE Air flow volume is determined from the differential pressure by the formula Volume cfm K ΔP the K factor of the VAV box multiplied by the square root of the differential pressure in wc The K factor should be in the information supplied by the VAV box s manufacturer For CSP 4702 specifications see the CSP 4702 Data Sheet For information on mount...

Страница 20: ... and limits were set in the CSP 500x the limits will need to be set in either the CSP 4702 or the thermostat If a CSP 4702 is used to replace an existing CSP 500x and limits were set in the thermostat the limits in the thermostat should be checked and adjusted to ensure ac curacy The terminals on the CSP 4702 terminal strips are in a different order than on a CSP 500x Override to Fully Closed show...

Страница 21: ... a CEP 4xxx an attached SSE xxxx sensor must be replaced with an SSS 1xxx sensor For an existing SSE 200x used for duct temperature sensing terminals X and Y can continue to be used for duct temperature sensing and an SSS 1xxx air flow sensor can be installed separately If a CSP 4702 is used to replace an existing CxP 4xxx and limits were set in the CxP 4xxx the limits will need to be set in eithe...

Страница 22: ... made at the thermostat or at the controller For cooling select Sequence 1 from the CTE 5202 SYSTEM menu See Change Configuration on page 6 Heating Air Heating Max Heating Min Setpoint Colder Room Temperature Warmer Cooling Max Cooling Min Air Flow Air Flow Setpoint Colder Room Temperature Warmer AO1 Signal Cooling Air AO1 Signal Select Sequence 1 Select Sequence 1 AND Set Changeover to 55 F For h...

Страница 23: ...Open In the relay position shown below Open the controller will override the flow setting Jump ing 2 10 IN and 16 VDC OUT drives the CSP 4702 fully open NOTE If a maximum limit was set in the CSP 4702 controller the damper will only open to the maximum limit setting See also the Operation Test section of the CSP 4702 Installation Guide When the relay switches to Auto the thermostat will then contr...

Страница 24: ...w setpoint the first stage of reheat begins As the temperature continues to drop the second stage and later the third stage begin as needed Select Sequence 2 from the CTE 5202 SYSTEM menu with or without Auxiliary Flow AO1 AUX in LIMITS menu See Change Configuration on page 6 NOTE Triac outputs on the REE 5001 are for 24 VAC loads only The phase side of the transformer connects to the common side ...

Страница 25: ...ADVANCE SETBACK menu See Change Configuration on page 6 and Unoccupied Standby Setback on page 5 NOTE The night unoccupied setback offset does not apply to morning warm up NOTE This configuration requires the system fan to be on during setback setup mode NOTE Triac outputs on the REE 5001 are for 24 VAC loads only The phase side of the transformer connects to the common side of the load contactors...

Страница 26: ...wer than changeover temperature switches control to cooling mode Select Sequence 1 from the CTE 5202 SYSTEM menu See Change Configuration on page 6 and Hot Cold Changeover on page 5 The default changeover temperature is 77 F configurable from 55 to 85 F in the CTE 5202 ADVANCE menu NOTE Minimums can be set at zero air flow but a minimum of greater than zero is required for a quick changeover 2 F 2...

Страница 27: ...TE 5202 SYSTEM menu See Change Configuration on page 6 Hot Cold Changeover on page 5 and Cooling with Heating Changeover on page 26 See also Cooling and 3 Stage Reheat on page 24 2 F Of Loop 10 2 F 2 F AO1 MIN AO1 MAX AO1 MAX AO1 RA HOT AIR SEQUENCE Morning Warm Up AUX AO1 MIN COLD AIR SEQUENCE 0 Volts 12 Volts AO2 Disabled 0 Volts Temp Increasing Cooling Setpoint Heating Setpoint Heating Setpoint...

Страница 28: ...AO1 RA HOT AIR SEQUENCE Morning Warm Up AUX AO1 MIN COLD AIR SEQUENCE 0 Volts 12 Volts AO2 Disabled 0 Volts Temp Increasing Cooling Setpoint Heating Setpoint Heating Setpoint Hot Water Reheat AO2 RA AO1 DA When there is hot air in the duct changeover initi ates allowing the heating signal from AO1 to control airflow and AO2 to control the valve When there is a call for heat the thermostat modulate...

Страница 29: ...valve in place of the REE 5001 relay AO1 controls airflow and AO2 controls the valve When there is a call for heat the thermostat modulates the hot water valve Select Sequence 2 2 F Of Loop 10 2 F AO1 MAX AUX AO1 MIN COLD AIR SEQUENCE 0 Volts 12 Volts Temp Increasing Cooling Setpoint Heating Setpoint Hot Water Reheat AO2 RA AO1 DA MEP 4002 Actuator on VEB 43 46 Series Valve 24 VAC Common Input Out...

Страница 30: ...ase in voltage on AO2 and starts the fan As the temperature continues to drop the first stage of reheat begins and the second stage of reheat follows if the thermostat is still not satis fied The process reverses as the room temperature begins to rise Sequence 1 should be selected from the CTE 5202 SYSTEM menu See Change Configuration on page 6 NOTE The REE 5002 provides the fan an adjustable star...

Страница 31: ... 5202 In this application the CSP 4702s are mounted separately on the cold and hot air duct dampers with each using its own flow sensor The cold deck controller receives the AO1 signal from the thermostat while the hot deck controller receives its requested flow signal from AO2 Both CSP 4702s can be set independently for minimum and maximum flow settings Select Sequence 3 from the CTE 5202 SYSTEM ...

Страница 32: ...ault direction is used in the examples of this section See also the CSP 5001 5002 Applications Guide Concerning replacements of the CTE 510x thermo stats see Cross References on page 8 To manually open the box remove wiring from Terminal IN and jumper Terminal IN to Terminal 16 VDC This will tell unit to control at 3300 fpm full airflow the green LED should turn on and the box should drive open To...

Страница 33: ...the CTE 5202 SYSTEM menu See Change Configuration on page 6 This replaces a CTE 5101 or a CTE 5015 Heating Air Heating Max Heating Min 1650 fpm 0 fpm Setpoint Colder Room Temperature Warmer 3300 fpm Cooling Max Cooling Min 1650 fpm 0 fpm Setpoint Colder Room Temperature Warmer 3300 fpm AO1 Signal Cooling Air AO1 Signal Select Sequence 1 Select Sequence 1 AND set Changeover to 55 F For heating conn...

Страница 34: ... Fully Closed In the relay position shown below the controller will override the flow setting Jumping and IN drives the CSP 5001 fully closed NOTE If a minimum limit was set in the CSP 500x controller the damper will only close to the minimum limit setting When the relay switches to Auto the thermostat will then control the VAV box based on demand The Override to Fully Open wiring illustration bel...

Страница 35: ...first stage of reheat begins As the temperature continues to drop the second stage and later the third stage begin as needed Select Sequence 2 from the CTE 5202 SYSTEM menu with or without Auxiliary Flow AO1 AUX in LIMITS menu See Change Configuration on page 6 See also the Cooling with 3 Stage Reheat section with a CTE 5104 for auxiliary flow or a CTE 5103 without auxiliary flow in the CSP 5001 5...

Страница 36: ...ccupied setback setup signal from other equipment not shown When the contact is closed e g by a timer setback setup mode initiates changing the setpoint by the offset selected in ADVANCE SETBACK menu See Change Configuration on page 6 and Unoccupied Standby Setback on page 5 NOTE The night unoccupied setback offset does not apply to morning warm up NOTE This configuration requires the system fan t...

Страница 37: ...perature is 77 F configurable from 55 to 85 F in the CTE 5202 ADVANCE menu NOTE The CTE 5202 uses the 16 VDC power from the CSP 5001 If replacing a CTE 5103 thermostat as described in the Cooling and Heating Changeover section of the CSP 5001 5002 Applications Guide the REE 1005 relay module is no longer needed with the CTE 5202 NOTE If using an existing TTE 2001 duct sensor transmitter instead of...

Страница 38: ...or 2 F Of Loop 10 2 F 2 F AO1 MIN AO1 MAX AO1 MAX AO1 RA HOT AIR SEQUENCE Morning Warm Up AUX AO1 MIN COLD AIR SEQUENCE 0 Volts 12 Volts AO2 Disabled 0 Volts Temp Increasing Cooling Setpoint Heating Setpoint Heating Setpoint 9 5 V 3 5 V 3 1 6 5 V 2 Reheat Stages AO2 RA AO1 DA NOTE The CTE 5202 uses the 16 VDC power from the CSP 5001 If replacing a CTE 5103 thermostat as described in the Cooling wi...

Страница 39: ... T AI1 AO1 AO2 CTE 5202 Thermostat CSP 5001 Controller Actuator H 16 V DC I N O U T L 24 VAC To Flow Sensor 24 VAC 9 VA Phase Neutral 1 2 3 TTE 2001 or STE 140x Duct Sensor MEP 4002 Actuator on VEB 43 46 Series Valve 24 VAC Common Input Out 2 F Of Loop 10 2 F 2 F AO1 MIN AO1 MAX AO1 MAX AO1 RA HOT AIR SEQUENCE Morning Warm Up AUX AO1 MIN COLD AIR SEQUENCE 0 Volts 12 Volts AO2 Disabled 0 Volts Temp...

Страница 40: ... REE 5001 relay To retrofit a CTE 510x thermostat in an existing installation with a different valve than a VEB 43 46 series see the corresponding installation guide for that valve and actuator AO1 controls airflow and AO2 controls the valve When there is a call for heat the thermostat modulates the hot water valve See also the Cooling with Hot Water Reheat section with a CTE 5104 in the CSP 5001 ...

Страница 41: ...TE 5202 SYSTEM menu See Change Configuration on page 6 T T AI1 AO1 AO2 CTE 5202 Thermostat CSP 5001 Controller Actuator H 16 V DC I N O U T L 24 VAC REE 5002 Relay Module To Flow Sensor 24 VAC 34 VA 24 VAC Contactors 10 VA Max per Stage Heat Stage 1 Fan Phase Neutral 24 VAC Fan 1 2 Stages X T Load Heat Stage 2 See also the Fan Induction with 2 Stage Electric Heat section with a CTE 5101 in the CSP...

Страница 42: ...sted flow signal from AO2 Both CSP 5001s can be set independently for minimum and maximum flow settings T T AI1 AO1 AO2 CTE 5202 Thermostat CSP 5001 Controller Actuator H 16 V DC I N O U T L 24 VAC To Flow Sensor 24 VAC 8 VA Phase Neutral CSP 5001 Controller Actuator H 16 V DC I N O U T L 24 VAC To Flow Sensor Cold Deck Hot Deck Select Sequence 3 from the CTE 5202 SYSTEM menu See Change Configurat...

Страница 43: ...cations which requires an additional relay module The CSP 4000 series uses SSS 1000 series differential air flow sensors or a pitot tube instead of the SSE 1000 2000s Otherwise wiring is the same as with the CEP 4000 series used in these examples To manually drive the controller damper open or closed with 24 VAC on terminals 9 and 10 remove the wiring to terminal 6 and temporarily jumper terminal ...

Страница 44: ...m However this will still cover nearly all applications See the Voltage Velocity Correlation chart in the CEP 4000 Series Applications Guide T T AI1 AO1 AO2 CTE 5202 Thermostat 24 VAC 10 VA Phase Neutral 7 6 5 4 3 2 1 8 9 10 11 12 13 14 CEP 4xxx Controller Actuator 24 VAC Power to CTE 5202 9 1 VDC Power to CTE 5202 OR but NOT Both If more than about 2000 fpm is required use 24 VAC from a transform...

Страница 45: ...can use CEP CSP 4000 series electronic VAV controllers to operate damper boxes in a pressure independent VAV system As shown in the diagram a requested flow voltage signal AO1 is connected to the CEP 4xxx to adjust airflow from minimum to maximum flow according to space demand Minimum and maximum flow limit adjustments can be made at the thermostat or at the controller Select Sequence 1 from the C...

Страница 46: ...e air flow to fully open for morning warm up Otherwise the example below is the same as the configuration in Cooling on page 45 The SPDT relay selects one of the two modes Auto or Fully Open Terminal 6 on the CEP 4xxx is connected to either Terminal 5 Fully Open or to AO1 on the CTE 5202 Auto the default When Terminal 6 is connected to Terminal 5 the 9 1 VDC causes full flow See also the Cooling w...

Страница 47: ...iguration on page 6 This replaces a CTE 1004 or a CTE 5002 5012 thermostat If no Auxiliary Flow is desired set AO1 AUX to 0 in the LIMITS menu T T AI1 AO1 AO2 CTE 5202 Thermostat 24 VAC 40 VA Phase Neutral 1 2 3 7 6 5 4 3 2 1 8 9 10 11 12 13 14 CEP 4xxx Controller Actuator SSE 1001 1002 Flow Sensor REE 4001 5001 Relay Module 24 VAC 3 2 1 Stages 3 Stage Reheat T 24 VAC Contactors 10 VA Max per Stag...

Страница 48: ...ure switches control to cooling mode Select Sequence 1 from the CTE 5202 SYSTEM menu See Change Configuration on page 6 and Hot Cold Changeover on page 5 The default changeover temperature is 77 F configurable from 55 to 85 F in the CTE 5202 ADVANCE menu NOTE If replacing a CTE 1103 thermostat as described in the Cooling Heating Change over section of the CEP 4000 Series Ap plications Guide or a C...

Страница 49: ...REE 4006 relay module have been discontinued Replacement actuators MEP 3001s for those valves are still available as of Oct 2012 The REE 4006 can be replaced by an REE 4106 or REE 5106 which have built in power supplies that could be used to power the CTE 5202 if desired See also use of a VEB 43 46 valve in Cooling with Hot Water Reheat on page 40 2 F Of Loop 10 2 F AO1 MAX AUX AO1 MIN COLD AIR SE...

Страница 50: ...crease in voltage on AO2 and starts the fan As the temperature continues to drop the first stage of reheat begins and the second stage of reheat follows if the thermostat is still not satis fied The process reverses as the room temperature begins to rise Sequence 1 should be selected from the CTE 5202 SYSTEM menu See Change Configuration on page 6 See also the Fan Box with Reheat section with a CT...

Страница 51: ...lave controller to exhaust 550 fpm 4 1 VDC The amount of voltage offset would be 0 10 VDC to set up the REE 1013 See the Voltage Velocity Correlation section in the CEP 4000 Series Applications Guide With the REE 1013 the maximum offset is 2 VDC as measured by a voltme ter between the and terminals T T AI1 AO1 AO2 CTE 5202 Thermostat 24 VAC 20 VA Phase Neutral 1 2 3 7 6 5 4 3 2 1 8 9 10 11 12 13 1...

Страница 52: ...e CEP 4000 Series Applications Guide T T AI1 AO1 AO2 CTE 5202 Thermostat 24 VAC 20 VA Phase Neutral 1 2 3 7 6 5 4 3 2 1 8 9 10 11 12 13 14 CEP 4xxx Controller Actuator SSE 1001 1002 Flow Sensor 1 2 3 7 6 5 4 3 2 1 8 9 10 11 12 13 14 SSE 1001 1002 Flow Sensor CEP 4xxx Controller Actuator Hot Deck Cold Deck Select Sequence 3 Cooling Max Cooling Min 0 fpm Colder Room Temperature Warmer 3000 fpm Air F...

Страница 53: ... reset by the room thermostat A second slave controller is mounted on the hot air duct as a constant volume unit with the flow sensor measuring downstream total flow into the space The slave controller has no reset from the thermostat As the cold deck resets from maximum to minimum flow the hot deck controller senses a decrease in total flow to the space opens the hot air duct to compensate and th...

Страница 54: ... MP 52xx beer can actuators TP 8101 TP 8102 and TP 8103 Leads and Terminals Function CTE 5202 Terminals Red Wire Lead 20 VDC Phase Yellow Wire Lead Proportional Output AO1 Blue Wire Lead Common T Common Terminal 1 Common T Common Terminal 2 Auxiliary Input AI1 NOTE Use Sequence 1 See sample applications on page 55 and page 56 TP 8124 and TP 8125 Terminals Function CTE 5202 Terminals OP2 2 15 VDC C...

Страница 55: ...1650 fpm 0 fpm Setpoint Colder Room Temperature Warmer 3300 fpm AO1 Signal Cooling Air AO1 Signal Select Sequence 1 Select Sequence 1 AND set Changeover to 55 F For cooling select Sequence 1 from the CTE 5202 SYSTEM menu See Change Configuration on page 6 For heating connect a 5K to 10K ohm resistor between Common and AI1 Select Sequence 1 and lower the Changeover to the lowest setting 55 F See Ch...

Страница 56: ...at Red 20 VDC Yellow IV1 Blue Common Red 20 VDC MP 52xx Series Actuators Yellow IV1 Blue Common Tape Red Lead if Present Red 20 VDC Controlled Device with Power Supply Yellow IV Blue Common MP 52xx Series Actuators See TP 8101 8102 8103 Replacement General on page 55 This is the same configuration except for the addition of MEP 52xx actuators and changes to the connections to the red leads ...

Страница 57: ...ice with Power Supply Red 20 VDC Controlled Device with Power Supply Yellow IV Blue Common Tape Red Leads if Present CTE 5202 thermostats can replace TP 8101 8102 8103 thermostats and use the 20 VDC supplied by a controlled device For more information see the manufacturer s installation guide for the controlled devices CAUTION Never connect together the red leads or 20 VDC terminals of controlled ...

Страница 58: ...ed 20 VDC Controlled Device with Power Supply Yellow IV Blue Common MP 52xx Series Actuator Cooling Red 20 VDC Controlled Device with Power Supply Yellow IV Blue Common Tape Red Lead if Present Red 20 VDC Yellow IV1 Blue Common MP 52xx Series Actuator Heating See TP 8124 8125 Replacement with One or No MP 52xx Actuators on page 57 This is the same configura tion except for having two MEP 52xx actu...

Страница 59: ...6 Cooling with Proportional Hot Water Reheat 49 C or F Temperature Scale 6 Cross Reference Barber Colman TP 81xx 8 54 KMC CTE 1x0x 8 KMC CTE 50xx 9 KMC CTE 510x 9 Other Thermostats 9 CSP 4000 CSP 40xx 42xx 44xx 46xx 21 43 CSP 4702 19 CSP 5001 5002 20 32 CTE 1x0x Cross Reference 8 CTE 50xx Cross Reference 9 CTE 510x Cross Reference 9 CTE 1001 Replacement 45 CTE 1004 Replacement 47 49 CTE 1101 Repla...

Страница 60: ... 4006 49 REE 4106 49 REE 5001 24 25 27 35 36 38 47 REE 5002 30 41 50 REE 5106 49 S Schneider Electric TP 81xx 54 Sequences 6 7 Setback 5 25 36 Setpoint Adjusting 6 Troubleshooting 10 Single Duct 16 19 32 45 Span 6 SSE 1001 1002 Flow Sensors 45 47 49 50 51 52 53 SSE 2001 2002 Flow Temp Sensors 46 48 Standby Setback 5 STE 140x Duct Sensor 37 38 39 STE 1454 1455 Strap On Temp Sensor 15 Support Files ...

Отзывы: