SMY133-SMY134-SMP133 Operating Manual
Digital Outputs & Digital Inputs
„R“-Type Outputs (relay)
model / outputs
“RR / RI”
/ “R”-outputs
“W”
/ RO1-2
type
relay, N.O. contact
load rating
250 V
AC
/ 30 V
DC
, 4 A
30 V
DC
, 4 A
„D“-Type Outputs (solid state, opto-MOS)
model / outputs
“RI / II”
/ “I”-outputs
“V / AA / AT”
/ DO1-4
typ
Opto-MOS, bipolar
Opto-MOS, unipolar
load rating
60 V
AC
/ 100 V
DC
, 100 mA
35 V
DC
, 100 mA
dynamic param. (pulse output) :
- pulse duration
- gap duration
- maximum frequency
S0 - compatible
50 ms
>= 50 ms
10 Hz
Digital Inputs
model
“RR / RI / II”
“V / W / AA / AT”
type
optoisolated, bipolar
optoisolated, unipolar
maximum voltage
100 V
DC /
/ 60 V
AC
35 V
DC
voltage for “logical “ 0 / 1
< 3 V
DC
/ > 10 V
DC
< 3 V
DC
/ > 10 V
DC
input current
1 mA @ 10V / 5 mA @ 24V /
10 mA @ 48V
3 mA @ 10V / 13 mA @ 24V /
20 mA @ 35V
dynamic parameters *) :
- pulse/gap duration
- maximum frequency
>= 50 / 50 ms
10 Hz
>= 0.5 / 0.5 ms
1 kHz
Note *) : Limit that correspond to the instrument hardware. Real values depend on the firmware filter adjustment -
see the chapter
Digital Input Filter
.