background image

The current signals from 5A or 1A (or 0.1A for the „X/100mA“ models) instrument current transformers must be connected to the 

CURRENT 

connector terminal pairs 

I11 – I12

I21 – I22

I31 –

 

I32 

(No. 1 ÷ 6). 

A particular connector is provided with a screw lock to prevent an accidental pullout and possible unwanted disconnection of the current circuit.
A connection cable maximum cross section area is 2.5 mm

2

.

1.2.4 Outputs

Instruments can have up to 18 outputs. For models with more than 9 outputs, the outputs are arranged in two output groups. The groups are isolated from each other. Each 
group has one common pole terminal 

C1, C2 

( No.15 and 25 ) and up to nine individual output terminals 

1.1

 through 

1.9

 ( No.16 ÷ 24 ) for group No. 1 and 

2.1

 through 

2.9

 

( No.26 ÷ 34 ) for group No. 2.
Any combination of compensation capacitors or chokes (three-phase, two-phase or single -phase) can be connected to the instrument outputs via appropriate contactors.
If not of all outputs used, you can use upper three outputs for alarm signalling or for heating/cooling control ( see example wirings further below).
A connection cable maximum cross section area is 2.5 mm

2

.

1.2.5 Digital Input

Models with 7 and 16 outputs are equipped with the digital input. It can be used for the 2

nd

 tariff control of power factor control process or  for electricity meter tariff control.

Use terminals 

D1A

D1B

 (No.23 and 24) for the digital input connection – see wiring examples in appropriate chapter further below. The input is isolated from other instrument

circuitry. 
To activate the output apply voltage of specified range to the terminals.

2. Commissioning

On connecting power supply, the instrument performs internal diagnostics, display test and then gradually shows screens with the instrument type and setting of basic 
parameters : instrument model and firmware version number, VT-ratio (if indirect voltage connection is set), CT-ratio and nominal frequency f

NOM

 and nominale voltage U

NOM

Then the instrument starts display actual measured values. Simultaneously, if the instrument has a communication line, it can be set and its measured values read via the 
communication link using a PC.
As, because of the first installation, the instrument knows neither output types nor reactive power sizes of individual outputs, it gets into the standby mode, which is signalled 
by flashing symbol 

.

If measuring voltage is present and measured current reaches at least minimum level, the instrument tries to start automatic output recognition ( AOR ) process that is 
indicated with flashing symbol 

 and the 

A

 

O

  

r

 message. As soon as it occurs, switch into instrument parameters with the 

 key. When parameters are displayed, the 

AOR-proces is cancelled and the controller stays in the standby mode until it returns back to measured quantities display – that occurs automatically after about 30 seconds if
no key is pressed.
At this moment, before we let the AOR-process running it is necessary to set so called 

Installation

 parameters, that are essential for proper operation of the instrument.

2.1 Measured Electrical Quantities Installation Setup

For proper data evaluation it is necessary to set the 

Installation Setting

 group parameters, starting from parameter 71 up :

CT- ratio

 ( p. 71 ). Can be set in form either  …/ 5A or …/ 1A.

Furthermore, so called  

I-Multiplier

  can be set too. You can modify the CT- ratio with this parameter. For example, to get better precision when using 

overweighted CTs, you can apply more windings of measured wire through the transformer. Then you must set the multiplier. For example, for 2 windings 
applied, set the multiplier to 1/2 = 0.5 .

For standard connection with 1 winding, the multiplier must be set to 1. 

Connection Type

 ( p. 72 ) needs to be set according network configuration – wye ( or star, 

 

3

 

Y

 

) delta ( 

3

 

d

 

, if neutral voltage potential not connected ), 

or Aron ( 

3

 

A

 

 

). For single-phase connection, set

1

  

Y

 

3

  or 

1

 

d

 

3

.

Connection Mode

 ( parameter 74 ) determines if voltage signals are connected directly (

 

-

 

-

 

-

 

) or via voltage transformers. In such case the 

VT

-ratio 

must be set.

The VT-ratio must be set in form 

Nominal primary voltage / Nominal secondary voltage

. For very high primary voltages 

the U-Multiplier

  must be used. 

Nominal frequency 

f

NOM 

 ( p. 75 ) must be set in compliance with the measurement network nominal frequency to either 50 or 60 Hz.

Nominal Voltage U

NOM

 

( p. 75 ) 

and Nominal Power P

NOM  

( p. 76 ) :  For the presentation of voltages and powers in percent of nominal value, voltage alarms 

operation and other functions it is necessary to enter also the nominal ( primary ) voltage of the measured mains 

U

NOM

 and nominal apparent three-phase 

Содержание NOVR 2400

Страница 1: ...Full scale Operating Manual containing detailed description of all features can be free downloaded from manufacturer s website www kmbsystems eu Ta skr cona instrukcja obs ugi regulatora NOVAR 2400 za...

Страница 2: ...rder of magnitude of amperes This fact needs to be kept in mind when selecting the primary protection devices 1 2 2 Measured Voltages Connect measured voltages in wye star delta or Aron configuration...

Страница 3: ...ument knows neither output types nor reactive power sizes of individual outputs it gets into the standby mode which is signalled by flashing symbol If measuring voltage is present and measured current...

Страница 4: ...w to the parameter branch with the button The branch is indicated with the symbol Parameter 01 appears target power factor control bandwidth Now scroll down with the key to parameter 71 that is the CT...

Страница 5: ...ecially at high voltage compensation systems where discharge time in range of minutes must be set Optionally you can set any of the highest three of outputs as alarm fan control or heater control Now...

Страница 6: ...cates that setup data are displayed now The parameters are arranged in groups numbered from 00 up The number of group is displayed in the first line in format P n n with preceding dash You can browse...

Страница 7: ...min 30 sec No L control time reduction by squared proportion L linear c time reduction 03 offset power tariff 1 any 0 Value corresponds to UNOM specified Displayed when offset control set only 05 tar...

Страница 8: ...temperature threshold C line 3 off temperature threshold C fan 10 60 C heater 30 10 C fan 40 C heat 5 C Skipped if appropriate output control state different from fan heater 31 the antepenultimate ou...

Страница 9: ...PF control failure undercompensated PFfh PFfhAVG cos 0 00 C L 1 00 1 sec 20 min PFfh 0 95L 1 min indication only Notes In CT secondary rated current 5A or 1A according the CT ratio setup Installation...

Страница 10: ...5 255 255 0 10 0 0 138 parameters placed in side branch 89 instrument status read only row 2 failure specification row 3 serial no instr version scroll 0 255 0 r 2 0 failure free r 3 S serial no F fir...

Страница 11: ...szej tabeli Po czenie mierzonych napi napi cia grupy zacisk w Napi cie na Typ po czenia zaciskach gwiazda 3Y tr jk t 3D Aron 3A U1 L1 napi cie fazowe L1 napi cie fazowe L1 napi cie fazowe U2 L2 napi c...

Страница 12: ...ymbol i wiadomo A O r Jak najszybciej za pomoc przycisku prze cz si na parametry instrumentu Kiedy parametry s wy wietlone AOR proces zosta odwo any i regulator pozostaje w trybie czuwania a powr ci d...

Страница 13: ...dycji za pomoc kr tkiego naci ni cia Warto jest przechowywana w pami ci instrumentu a b yskanie zostaje zatrzymane Zmiana CT post powanie przyk ad Teraz powr do tzw g wnej ga zi parametru przy nast pn...

Страница 14: ...ocesu AOR uruchomi W zwi zku z tym konieczne jest aby wy czy ten alarm czasowo i w czy go ponownie po zako czeniu procesu AOR 2 2 2 1 Proces AOR Po uruchomieniu procesu pojawia si ekran AOR w pierwszy...

Страница 15: ...niekt rych parametr w Mo esz tak e u y funkcji automatycznego ponownego sprawdzania przytrzymuj c jeden z klawiszy strza ek Na koniec naci nij i ustawiona warto zostanie zapisana w pami ci urz dzenia...

Страница 16: ...zam wienie na t napraw Dystrybutor ENERVAR Artur Polegaj ul Staszica 13C 67 100 Nowa S l tel 48 604 554 551 email enervar e pl Przegl d parametr w PFC Kontrola grupa parametr w zakres ustawienia warto...

Страница 17: ...lonemu UNOM 26 wyj cie stan No 1 1 2 9 w bocznej ga zi kontrola w czony wy czony alarm wentylacja grzanie kontrola Opcje wentylacji ogrzewania i alarmu dost pne s tylko na trzech g rnych wyj ciach 27...

Страница 18: ...0 5 sec Sta e sekcje nie dotyczy uruchomienia 49 10 PF PF awaria sterowania PF odchylenie regulacji Qfh QfhAVG 1 sec 20 min QfhAVG 5 min I Tylko wskazanie 50 11 NS liczba operacji czeniowych przekroc...

Страница 19: ...a linia 2 dla grupy U I linia 3 dla grupy P Q S 0 01 60 1 sec 60 min 1 min 15 min metoda okna swobodnego domy lna 78 okres u redniania dla MD tryb wy wietlania licznika energii line 2 okres u redniani...

Страница 20: ...1A Typ p ipojen nap t a proud je t eba zadat ve skupin parametr Instalace k d zna po et p ipojen ch f z 3Y zna t f zov p ipojen do hv zdy 3D do troj heln ka 3A zna Aronovo zapojen P i nastaven 1Y3 i 1...

Страница 21: ...oby posledn ho stisku n kter ho tla tka P edt m ne nech me proces AOR prob hnout je t eba nastavit skupinu parametr tzv parametry instalace kter jsou podstatn pro spr vnou funkci p stroje 2 1 Nastaven...

Страница 22: ...se dal m stiskem vr t me do tzv hlavn v tve parametr viz popis d le a pomoc tla tek a m eme nalistovat dal parametr i skupinu parametr a obdobn m zp sobem nastavit jejich hodnotu Zp t do v tv m en ch...

Страница 23: ...l tor postupn odepne v echny regula n v stupy tj v echny mimo t ch kter jsou nastaven jako pevn nebo do funkce alarm ventil tor topen Pak p stroj ek dokud neuplyne nastaven doba blokov n znovuzapnut v...

Страница 24: ...dav Nejprve se vybere hodnota prvn ho parametru Pokud chcete m nit pouze nastaven druh ho z nich jednodu e ukon ete re im editace prvn ho parametru bez jeho zm ny a vstupte do editace znova nyn se vy...

Страница 25: ...racov n doby regulace 03 ofsetov v kon tarif 1 libovoln 0 Hodnota odpov d nastaven mu UNOM Zobrazen jen p i nast reg s ofsetem 05 funkce tarifu 2 aktu ln tarif dek 2 aktu ln tarif stav dek 3 funkce ta...

Страница 26: ...astaviteln parametr Lze pouze nulovat 29 teplotn meze sp n n v tr ku topen posledn ho v stupu dek 2 teplotn mez sepnut on C dek 3 teplotn mez vypnut off C v tr k 10 60 C topen 30 10 C v tr k 40 C tope...

Страница 27: ...in 0 5 sec pevn v stupy neovlivn ny 49 10 PF chyba kompenzace reg odchylka mimo reg p smo Qfh QfhAVG 1 sec 20 min QfhAVG 5 min I pouze indikace 50 11 NS p ekro en po tu sepnut po et sepnut stup 1 9999...

Страница 28: ...999 MVA 77 d lka okna pr m rov n dek 2 pro skupinu U I dek 3 pro skupinu P Q S 0 01 60 1 sec 60 min 1 min 15 min v choz zp sob pr m rov n typu plovouc okno 78 pr m rov n MD form t zobrazen elektrom ru...

Страница 29: ...Measured Quantities Branch Navigation Chart Rzeczywiste dane wykres nawigacji V tev m en ch veli in naviga n mapa prvn st...

Страница 30: ...nued Rzeczywiste dane wykres nawigacji kontynuowane V tev m en ch veli in naviga n mapa pokra ov n Electricity Meter Optional Display Format 8E Licznik energii elektrycznej opcjonalny format wy wietla...

Страница 31: ...Fundamental Harmonic Quantities Branch Navigation Chart Ga zmiennych podstawowych sk adowych harmonicznych wykres nawigacji V tev veli in z kladn harmonick slo ky naviga n mapa...

Страница 32: ...a P klady zapojen NOVAR 2400 R18 Typical Installation Direct Star 3Y Connection 18 Contactor Sections Typowa instalacja bezpo rednio pod czenie gwiazda 3Y 18 sekcji stycznik w Typick zapojen p m p ipo...

Страница 33: ...3Y Connection 14 Contactor Sections 2nd Tariff Control Fan Alarm Bezpo rednio pod czenie gwiazda 3Y 14 sekcji stycznik w 2nd taryfa wentylacja alarm P m p ipojen nap t do hv zdy 3Y 14 styka ov ch stup...

Страница 34: ...ence fNOM nominal nominalna nomin ln 50 60 Hz measuring range zakres pomiaru m ic rozsah 40 70 Hz measuring uncertainty b d pomiaru nejistota m en 10 mHz Voltage Napi cie Nap t ULN measuring range zak...

Страница 35: ...es pomiaru m ic rozsah 0 20 measuring uncertainty b d pomiaru nejistota m en 0 5 Measured Quantities Mierzone wielko ci M en veli iny Current Pr d Proud measuring range zakres pomiaru m ic rozsah 0 00...

Страница 36: ...M reference conditions warunki odniesienia referen n podm nky A ambient temperature temperatura otoczenia teplota okol tA U I for active p moc czynna inn v PF cos for reactive power moc bierna jalov v...

Страница 37: ...zat en 250 VAC 4 A 30 VDC 4 A Transistors Tranzystory Tranzistory T output type models Modele typu wyj T Modely s v stupy typu T type typ typ Opto MOS load rating obci enie maxim ln zat en max 100 VD...

Страница 38: ...kV EN 61000 4 5 2 kV EN 61000 4 6 3 V EN 61000 4 11 5 periods EMC emissions emisja vyza ov n EN 55011 class A not for home use nie do u ytku domowego nen ur en do bytov ho prost ed service communicat...

Отзывы: