For example: in the main branch, while showing parameter group 25 (section powers), you will see :
-
P
2
5
- parameter group number with the preceeding dash indicating the main branch
1
.
1
- number of the 1st output section
2
4
.
5
- section 1.1 power : three phase capacitor of 24.5 kvars
Pressing the
key you switch to the side branch and the screen changes as follows :
P
2
5
- parameter group number without the dash
-1
.
1
- number of the output with the preceeding dash indicating the side branch
Now you can move up and down in the side branch with with the
or
keys through all sections’ values.
Pressing the
again returns display to the main branch (the dash returns to the 1st line).
You can find overview of all the instrument parameters in tables below.
Parameter List
PFC - Control
#
parameter group
range
default
comment
01
target PF & bandwidth, tariff 1
line 2 : target PF (cos/tan/φ)
line 3 : control bandwidth
- 0.80 ÷ 0.80 (cos)
0.000 ÷ 0.040 (cos)
(cos)
0.98
0.010
Other available formats : „tan“, „φ“.
Toggled with the
key.
02
control time UC/OC, tariff 1
line 2 : c. time at undercompensation (UC)
line 3 : c. time at overcompensation (OC)
5 sec ÷ 20 min
5 sec ÷ 20 min
3 min
30 sec
No “
L
”: control time reduction by
squared proportion
“
L
”: linear c. time reduction
03
offset power, tariff 1
any
0
Value corresponds to
U
NOM
specified.
Displayed when offset control set only.
05
tariff 2 control & actual tariff
line 2 : actual tariff (state)
line 3 : tariff 2 control
t=1 / t=2
OFF / dig.input (InP) / power (P)
OFF
Actual tariff is not any presetable
parameter; it indicates actual tariff state
only
06
target PF & bandwidth, tariff 2
line 2 : target PF (cos/tan/φ)
line 3 : control bandwidth
- 0.80 ÷ 0.80 (cos)
0.000 ÷ 0.040 (cos)
(cos)
0.98
0.010
Other available formats : „tan“, „φ“.
Toggled with the
key.
07
control time UC/OC, tariff 2
line 2 : c. time at undercompensation (UC)
line 3 : c. time at overcompensation (OC)
5 sec ÷ 20 min
5 sec ÷ 20 min
3 min
30 sec
No “
L
”: control time reduction by
squared proportion
“
L
”: linear c. time reduction
08
offset power, tariff 2
any
0
Value corresponds to
U
NOM
specified.
Displayed when offset control set only.
10
tariff 2 control power
0 ÷ 120 %
P
NOM
0
Displayed when tariff 2 control set to
power only.
11
control strategy
3p+1p (31P) / 3p (3P) /
3*1p (1P)
3p+1p
(31P)
12
choke control & choke control limit PF
line 2 : choke control
line 3 : choke control limit power factor
OFF / mixed (M) / non-mixed (nM)
- 0.80 ÷ 0.80 (cos)
OFF
1.0
Choke control limit power factor
displayed when choke control set to
mixed only.
13
offset control
OFF / On
OFF