PFC - Outputs
#
parameter group
range
default
comment
20
automatic output recognizer (AOR) starting
OFF / auto (A)
auto
Furthermore, the AOR can be launched
manually with the „run“ option.
21
manual filler; 3 subparameters :
1. min. output type & nom. power (
O
MIN
)
2. output ratio
3. count of outputs
any
11111 ÷ 12488
0 ÷ 18
1 kvar
11111
0
25
output type & nominal power,
No.1.1 ÷ 2.9 in subparameters
any
0
Value corresponds to
U
NOM
specified.
26
output control state
No.1.1 ÷ 2.9 in subparameters
control / fixed-on / fixed-off /
fan / heating / alarm-on / alarm-
off
control
Fan, heating and alarm options available
at three upper outputs only
27
output switching operations count
No.1.1 ÷ 2.9 in subparameters
-
-
Not a presetable parameter. Can be
cleared only.
28
output switch-on time [hours]
No.1.1 ÷ 2.9 in subparameters
-
-
Not a presetable parameter. Can be
cleared only.
29
the ultimate output fan/heater temperature thresholds
line 2 : “on” temperature threshold [°C]
line 3 : “off” temperature threshold [°C]
fan : +10 ÷ +60 °C
heater : -30 ÷ -10 °C
fan: +40°C
heat.: -5°C
Skipped if appropriate output control
state different from fan / heater.
30
the penultimate output fan/heater temperature thresholds
line 2 : “on” temperature threshold [°C]
line 3 : “off” temperature threshold [°C]
fan : +10 ÷ +60 °C
heater : -30 ÷ -10 °C
fan: +40°C
heat.: -5°C
Skipped if appropriate output control
state different from fan / heater.
31
the antepenultimate output fan/heater temperature thresholds
line 2 : “on” temperature threshold [°C]
line 3 : “off” temperature threshold [°C]
fan : +10 ÷ +60 °C
heater : -30 ÷ -10 °C
fan: +40°C
heat.: -5°C
Skipped if appropriate output control
state different from fan / heater.
33
output set 2
OFF / 1.2 ÷ 2.9
OFF
34
set1 (& set2) discharge time
line 2 : set1 discharge time
line 3 : set2 discharge time
5 sec ÷ 20 min
20 sec
If the output set2 zero the set1
discharge time displayed only.
35
switching mode
intelligent / circular / linear
int.
PFC - Alarms
#
alarm No.,
mark
alarm event
control
quantity / event
limit setting range
activation (/ deact.)
delay
default v.
I
ndication,
A
ctuation
notes
40
01
U<<
voltage loss
U
LN
(1 period)
20% of U
NOM
(fixed)
0.02 sec / 5 sec (fixed)
-
I
+
A
simultaneous
disconnection
41
02
U<
undervoltage
U
LN
/ U
LNAVG
20÷100% of U
NOM
1 sec ÷ 20 min
U
LN
/ 70 % / 1 min
42
03
U>
overvoltage
U
LN
/ U
LNAVG
100÷200% of U
NOM
1 sec ÷ 20 min
U
LN
/ 130 % / 1min
43
04
I<
undercurrent
I / I
AVG
0÷25.0 % of In *)
1 sec ÷ 20 min
I / 0.1 % / 5 sec
I
+
A
fixed sections
not affected by
actuation
44
05
I>
overcurrent
I / I
AVG
100÷140 % of In *)
1 sec ÷ 20 min
I / 120 % / 1 min
indication only
45
06
CHL>
CHL limit exceeded
CHL / CHL
AVG
80÷300 %
1 sec ÷ 20 min
CHL / 133 % / 1min