installation overvoltage class / level of
pollution
•
for voltage up to 300 V AC
III-2 in compliance with EN 61010-1
•
for voltage over 300 V AC
—
II-2 in compliance with EN 61010-1
Communication
interface
RS-485 / Ethernet 10/100 BASE-T,
galvanically isolated
transmission rate
4800 ÷ 19200 Baud
maximum number of instruments on one communication line
1/32
maximum node–to–node distance
30 metres / 1200 metres
data transfer protocol
KMB / Modbus RTU
Operating Conditions
working environment
class C1 in compliance with IEC 654-1
operating temperature
-40° ÷ +60°C
relative humidity
5 to 100 %
EMC
noise suppression level
in compliance with EN 50081-2,
EN 55011 , class A,
EN 55022 , class A
immunity
in compliance with EN 61000-6-2
Physical
parameter
Novar Model
1005 / 1007
1106 / 1114
1206 / 1214
1314
enclosure
•
front panel
IP40 ( IP54 option )
•
back panel
IP 20
dimensions
•
front panel
•
built-in depth
•
installation cutout
96 x 96 mm
80 mm
92
+1
x 92
+1
mm
144 x 144 mm
80 mm
138
+1
x 138
+1
mm
mass
max. 0.3 kg
max. 0.7 kg
Содержание NOVAR-1 Series
Страница 66: ...Novar 1xxx KMB systems 66 Novar1106 installation...
Страница 67: ...Novar 1xxx KMB systems 67 Novar1114 installation...
Страница 68: ...Novar 1xxx KMB systems 68 Novar1206 installation low voltage measurement...
Страница 69: ...Novar 1xxx KMB systems 69 Novar1214 installation high voltage measurement...
Страница 70: ...Novar 1xxx KMB systems 70 Novar1114 S400 installation...
Страница 71: ...Novar 1xxx KMB systems 71 Novar 1214 S400 installation controller and contactors supllied from DC...
Страница 72: ...Novar 1xxx KMB systems 72 Novar1312 installation hybrid system with both thyristor switches and contactors...
Страница 73: ...Novar 1xxx KMB systems 73 Novar1414 installation low voltage measurement...