Novar 1xxx
KMB systems
17
Fig. 2.2 : Novar1214 Controller – Connectors
L1
L2
L3
N
1
2
3
4
5
6
7
8
9
10
11
12
13
14
ALARM
5A
(1A)
max.
10A
100÷275 VAC
k
l
L
N
RS 232/485
Rx
TR
A
B GND
Tx GND
Made in Czech Republic
/
/
Serial / vers.:
Product. date :
IP 4X
U 100 275 VAC, 7VA,
÷
÷
43 67 Hz
SUPPLY
LOAD
58÷690 VAC
N
L
L/N
L
max. 6A
max. 6A
2. TARIF
2.2.1.2 “/S400” Version Controllers
Controllers of the “/S400” version can be supplied with higher voltage – up to 500 V, either AC or DC.
The power demand is the same as those of standard version.
The supply voltage connects to terminals 3 (
L1
) and 5 (
L2/N
). In case of DC supply voltage the
polarity of connection is generally free, but for maximum electromagnetic compatibility grounded pole
should be connected to the terminal 5 (
L2/N
); see connection examples below.
Power supply voltage needs to be externally protected ( see following chapter).
Despite of standard version, power supply terminal 3 (
L
)
is not
internally connected to the common
pole of output relays. Terminals 4 and 6 are not used.
Fig. 2.3 : Novar1114/S400 Controller – Connectors
L1
L2
L3
N
1
2
3
4
5
6
7
8
9
10
11
12
13
14
ALARM
5A
(1A)
max.
500
VAC
L2/N
RS 232/485
Rx
TR
A
B GND
Tx GND
Made in Czech Republic
/
/
NOVAR 1106 1114 / S400 / 232 485
Serial No / Fw. vers.:
Production date :
IP 4X
U 75 500 V AC, 7 VA,
÷
÷
43 67 Hz
SUPPLY
LOAD
k
l
1A
L1
2.2.1.3 Novar 1005 / 1007 Controllers
The supply voltage connects to terminals 4 (
L1
) and 3 (
N
). Power supply voltage needs to be
externally protected ( see chapter
Protection
below ).
Power supply terminal 4 (
L1
) is internally connected to the common pole of output relays. It is
necessary to dimension the power supply protection in consideration of output contactors’ power as
well.
Содержание NOVAR-1 Series
Страница 66: ...Novar 1xxx KMB systems 66 Novar1106 installation...
Страница 67: ...Novar 1xxx KMB systems 67 Novar1114 installation...
Страница 68: ...Novar 1xxx KMB systems 68 Novar1206 installation low voltage measurement...
Страница 69: ...Novar 1xxx KMB systems 69 Novar1214 installation high voltage measurement...
Страница 70: ...Novar 1xxx KMB systems 70 Novar1114 S400 installation...
Страница 71: ...Novar 1xxx KMB systems 71 Novar 1214 S400 installation controller and contactors supllied from DC...
Страница 72: ...Novar 1xxx KMB systems 72 Novar1312 installation hybrid system with both thyristor switches and contactors...
Страница 73: ...Novar 1xxx KMB systems 73 Novar1414 installation low voltage measurement...