1.10.1 Output State Indications
The array of LEDs at the top right of the front panel show the current state of output relays. Each LED
is assigned a number from 1 to 14, and if lit, they indicate closed contacts of the corresponding output
relay.
If a LED is flashing, it means the controller wants to connect the output, but it has to wait for the delay
time to elapse. The corresponding output relay contacts are open and they will be closed as soon as
the reconnection delay time has elapsed.
An exception is the power-up display test to check correct operation of all display elements. In this test
the display shows
TEST
and all indication LEDs come on and go out one by one. All output relays stay
open while the test is running.
1.10.2 Trend Indication
These LEDs show the magnitude of deviation of the true instantaneous reactive power in the power
system from optimum reactive power value which would correspond to the specified value of required
power factor.
If the deviation is smaller than a half of the reactive power value of the smallest capacitor, both LEDs
are dark. If the deviation is greater than a half of, but smaller than, the reactive power value of the
smallest capacitor, the corresponding LED flashes — if lagging (undercompensation), the
IND
LED
flashes; if leading (overcompensation), the
CAP
LED flashes. If the deviation exceeds the value of the
smallest capacitor, the corresponding LED is permanently lit.
Exceptions to these LEDs’ meanings are the following situations:
•
measurement U and I method of connection is not defined (parameter 16)
•
automatic connection configuration detection process is in progress
•
automatic section power recognition process is in progress
If the method of connection is not defined, both LEDs flash; they are dark in the other two situations.
1.10.3 Indication of Manual Mode
Flashing
Manual
LED indicates that the controller is in the manual mode. The controller’s automatic
control function is disabled.
If this LED is dark and display is in the
Measurement
mode, the controller is in its standard control
mode or it is carrying out automatic connection configuration detection process or automatic section
power recognition process.
1.10.4 Indication of Backfeed (Power Export)
If the controller knows of the method of connection (measurement voltage and current), that is if the
automatic connection configuration detection process has been completed successfully or the method
of connection has been entered manually, the
Export
LED indicates the power transmission direction.
If it is dark, the power is flowing from the assumed power supply to the appliance. If the LED is lit, the
power is flowing in the opposite direction.
1.10.5 Alarm Indication
An
Alarm
relay can be used for non-standard events signalling. This relay’s operation can be set up
as described further below ( parameter 30 ). At Novar 10xx controllers that haven’t dedicated alarm
relay it is necessary to select and set alarm relay function first ( parameter 26 ).
The
Alarm
LED indicates this relay’s condition, that is if the
Alarm
relay’s output contact is closed, the
LED flashes.
Содержание NOVAR-1 Series
Страница 66: ...Novar 1xxx KMB systems 66 Novar1106 installation...
Страница 67: ...Novar 1xxx KMB systems 67 Novar1114 installation...
Страница 68: ...Novar 1xxx KMB systems 68 Novar1206 installation low voltage measurement...
Страница 69: ...Novar 1xxx KMB systems 69 Novar1214 installation high voltage measurement...
Страница 70: ...Novar 1xxx KMB systems 70 Novar1114 S400 installation...
Страница 71: ...Novar 1xxx KMB systems 71 Novar 1214 S400 installation controller and contactors supllied from DC...
Страница 72: ...Novar 1xxx KMB systems 72 Novar1312 installation hybrid system with both thyristor switches and contactors...
Страница 73: ...Novar 1xxx KMB systems 73 Novar1414 installation low voltage measurement...